SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
EN F650 BLOCK F.CDR
2
2
F650
Di
g
ital Ba
y
Controll
e
r
R
R
METERING
52
3
3
1
1
1
79
51G
67G
67SG
67P
50SG 51SG
50IG
50N
51N
67N
59X
27X
59NH
25
3V_0
51PL/V
51PH/V
Monitorin
g
CLOSE
TRIP
50G
1
50BF
1
49
3
50PH
3
50PL
3
46
3
48
3
32FP
3
32
3
32N
3
3
BROKEN
CONDUCTOR
3
3
3
3
3
3
3
3
1
3
3
3
3
59
3
VTFF
1
27
3
47
3
3
81O
3
81R
3
81U
3
3
3
3
59NL
3
D
ev
ic
e
Numb
e
r
Function
25
S
y
nchrocheck
27/27X
Bus/Line Undervoltage
32 Sensitive
Directional
Power
32FP
Forward Power
32N
Wattmetric zero-sequence directional
46
Negative Sequence Time Overcurrent
47
Negative Sequence Voltage
48
Blocked Rotor
49
Thermal Image - overload protection
50 BF
Breaker Failure
50PH/PL
Phase Instantaneous Overcurrent (High/Low)
50N
Neutral Instantaneous Overcurrent
50G
Ground Instantaneous Overcurrent
50SG
Sensitive Ground Instantaneous Overcurrent
50IG
Isolated Ground Instantaneous Overcurrent
51N
Neutral Time Overcurrent
51G
Ground Time Overcurrent
51SG
Sensitive Ground Time Overcurrent
51PH/V
Voltage Restraint Phase Time Overcurrent
51PL/V
59/59X
Bus/Line Overvoltage
59NH/NL
Neutral Overvoltage - High/Low
67P
Phase Directional Overcurrent
67N
Neutral Directional Overcurrent
67G
Ground Directional Overcurrent
67SG
Sensitive Ground Directional Overcurrent
79
Autorecloser
81 U/O
Under/Over Frequenc
y
Broken Conductor
Detection
N/A
Load Encroachment
81R
Frequenc
y
Rate of Change
VTFF
VT Fuse Failure Detection
ANSI Device Numbers & Functions
These records are stored in non volatile
memory. Therefore, there is no need
for internal battery monitoring or
maintenance.
Trip circuit monitoring
\* !
complete supervision circuits for breaker
trip and closing coils and circuits. These
supervision inputs monitor both the
battery voltage level and the continuity of
the trip and/or closing circuits, applying
current through those circuits and
$ " %
to apply this feature it is necessary to
choose I/O board 1 option 2.
Communications
\*
three ports that operate independently.
Redundant ports are available for high
reliability applications:
Available protocols for rear port 1 and 2
are ModBus RTU, IEC 103 and serial DNP
3.0.
The third port is located in a removable
communications card. This plug-and-
play card can be easily changed in the
future as new standards arrive to the
market, thus providing a migration path
to the customer.
The protocol available for the third port
is DNP 3.0 over TCP/IP, UDP/IP, ModBus
=/% %[/ \*Y*##*5"
ő
Graphic 16 x 40 or text 4 x 20 LCD display
ő
Fluorescent backlight to improve visibility
ő
Multicolor programmable LEDs with label panel
ő
{! [
ő
Key control for easy navigation
ő
Ergonomic programmable keys
ő
Electrically isolated front USB communication port
User Interface
Functional Block Diagram
Summary of Contents for SecoVac Series
Page 1: ...GE Industrial Solutions 3 3kV 27kV Embedded Pole Vacuum Circuit Breaker ...
Page 2: ...3 3kV 27kV Embedded Pole Vacuum Circuit Breaker ...
Page 11: ...Description 07 SecoVac 3 3kV 27kV Embedded Pole Vacuum Circuit Breaker Applications ...
Page 41: ...Check List 37 SecoVac 3 3kV 27kV Embedded Pole Vacuum Circuit Breaker Check List 38 ...