Chapter 4
– Configuration
RPV311
88
RPV311-TM-EN-7
Figure 41: Relay signaling events configuration section
A
The L
OG
events text field allows user to enter a code used for signaling events.
for log references. The relays will stay closed during the time set
in the On time configuration (previous section). In order to combine several LOG
events to trigger the alarm, use “comma” to separate the LOG numbers, for instance:
709, 710.
B
The W
ARNINGS
check box allows user to select the following events for signaling:
Equipment not ready;
Primary power failure;
Equipment unsync;
Fault recorder lack of memory;
Disturbance recorder lack of memory;
Steady-state recorder lack of memory;
SOE recorder lack of memory;
Link communication failure;
Internal failure.
In this case, signaling is active while the problem that has generated the alarm is not
resolved.