RPV311
Chapter 4
– Configuration
RPV311-TM-EN-7
85
Figure 38: Steady-state recorder
– flicker configuration section
A
The I
DENTIFIER
field shows all the voltage circuits previously configured.
B
The T
YPE
field shows the circuit type.
C
The check box allows the selection of circuits to be included in the steady-state
record.
In the flicker recorder, up to 6 circuits can be selected at the same time.
15
Groups
Group setup allows the user to monitor voltage and current circuit information via
local interface or the Monitoring screen at the web interface operation.
It is not possible to monitor circuits that are not included in either group.
To add new groups fill in the following:
The I
DENTIFIER
text field allows user to enter a single code for the group being
defined (maximum 15 characters). No editing allowed;
The I
DENTIFIER
field shows all the circuits and channels previously configured;
The T
YPE
field shows the circuits type;
The check box allows user to include the preset circuits for the group
formation;
The <D
ESELECT
ALL
> button allows user to deselect all circuits marked;
The <S
ELECT
ALL
> button allows user to select all circuits;
The L
ENGTH
,
R0,
X0,
R1 and X1 text fields allow user to enter the transmission
line characteristics (length and impedance), for the fault location.
The RPV311 uses one-end impedance fault location based on the Takagi algorithm
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...