Chapter 4
– Configuration
RPV311
66
RPV311-TM-EN-7
6
Digital Channels
The acquisition is simultaneous and synchronized with a time resolution of 65.104
𝜇
s
at 60 Hz or 78.125
𝜇
s at 50 Hz. The polarity is user-programmable (active high, active
low).
Digital channels can be associated with physical electrical digital inputs or
associated with the detection of IEC61850 GOOSE messages. For details about the
GOOSE messages, see Chapter 11: GOOSE Message Detection. The level of the state
transitions for physical inputs can be seen in Chapter 17: Technical Specifications
It is possible to adjust denouncing of the digital input to eliminate the effect of
switching of the relay contacts. The debounce time has a 0 to 20ms with 1ms steps.
All transitions of the digital channels are stored in the sequence of events (SOE)
record.
To add a new digital channel, select the Digital Channels section and fill in the
following:
The I
DENTIFIER
text field allows user to enter a single code for the channel being
defined (maximum 15 characters). No editing allowed;
The I
NPUT
scroll box allows user to define the input to which each digital channel is
connected. No editing allowed;
The P
OLARITY
scroll box allows user to select the input logic level (normal or inverted);
D
EBOUNCING
TIME
: the RPV311 will only start a record once the binary activation time
has exceeded the debouncing time parameter.
Once the digital channel is created, it shows in the configuration interface menu.
When selecting the digital channel, a screen shows the characteristics of the digital
channel selected, as shown in
. It is possible to edit the polarity and the
debounce time.
Figure 25: Adding and editing digital channels
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...