RPV311
Chapter 4
– Configuration
RPV311-TM-EN-7
63
The I
NPUTS
scroll box allows user to select the inputs to which each measuring
element is connected. No editing allowed;
The N
OMINAL VALUE
text field allows user to enter a circuit rated voltage;
The R
ATIO
text fields allows user to enter ratio of power transformers for each input.
Once the circuit is created, it appears in the configuration interface menu. When
selecting the circuit, a screen shows the characteristics of the circuit selected, as
shown in Figure 22. It is possible to edit some parameters, such as nominal value and
transformation ratio.
The frequency is calculated individually for each circuit as long as the magnitude of
the voltage is over 10% of the nominal magnitude configured in the Voltage Circuit
window. The frequency track occurs within the range of Nominal Frequency ±5Hz.
Figure 22: Adding and editing voltage circuits
4
Current Circuits
Considering the input type configurations, it is possible to create current circuits with
1, 2, 3, or 4 elements.
The phase sequences of the circuits supported by the equipment are ABC, BCA, CAB,
CBA, BAC, and CBA and may be customized by the user in the Equipment Setup,
shown in Section 2.9. The default sequence is ABC.
To add a new current circuit, select the C
URRENT
C
IRCUITS
section and fill in the
following:
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...