RPV311
Chapter 4
– Configuration
RPV311-TM-EN-7
49
RPV311 to identify the UTC time using information from the signal or from the
manual configuration of the user:
When Auto (IRIGB with extensions) is selected the RPV311 shall use the
information of time zone sent within the IRIGB signal to recover the UTC
time.
When Manual is selected the RPV will not consider eventual time zones
within the IRIGB signal, and rather it will use the UTC time zone configured in
the Manual parameter to retrieve the UTC time. This option is used specially
when the IRIGB does not inform the time zone, so the RPV311 cannot
retrieve the UTC time unless we inform the time zone manually.
The time setting that the RPV will use for time stamping is configured on the screen
Internal Clock.
It is possible to configure 30 min time zones.
B
The NTP
F
ALLBACK SERVER
defines the IP address of the SNTP time server to be used
to provide time synchronism when the IRIG-B is not connected.
2.2.2
Internal Clock
On the screen the internal clock for time stamping the registers and logs is
configured, as well as day light saving configurations.The configurable settings are:
A
The T
IMEZONE
defines if time zone information is supplied by the IEEE1344
extensions of the IRIG-B signal, or if it is manually set.
When Auto is selected the RPV311 will use the same local time sent within
the IRIGB signal.
When Manual is selected the RPV311 will use the UTC time (retrieved using
information from the Time Source screen) and calculate the local time using
the UTC time zone configured on the Internal Clock screen.
B
The D
AYLIGHT SAVING TIME
defines if time information is supplied by IEEE1344
extensions of the IRIG-B signal, or if it is either manually set or disabled. If it is
manually set, it is possible to choose the date and time of the start and the end of the
DST period.
It is possible to configure 30 min time zones.
2.3
Communications
The RPV311 communication may be via Ethernet and serial ports. The equipment
may also operate as a gateway over a local subnet.
Optionally the user can choose between two types of Ethernet, optical and electrical.
Gateway setup will enable the RPV311 to communicate with other equipment
connected over a local subnetwork. The Gateway can be configured by accessing the
equipment gateway configuration section, shown in
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...