RPV311
Chapter 3
– Hardware Design
40
RPV311-TM-EN-7
F
Front Panel Indicators: Mains lights up when the module is powered-up. Ready
indicator lights up after the module self-test is completed. The Link1 indicator lights
up when active.
2.3
RA332
2.3.1
Key Features
Up to 16 analog inputs (voltage, current, DC transducers, probes);
Up to 32 digital inputs;
16-bit analog-to-digital converters, 256 points-per-cycle sampling rate;
Frequency response of DC to 3.0 kHz;
Fiber-optic interface to connect to the processing module;
Up to 2 km fiber-optic links;
Front panel mounting or internal panel mounting.
2.3.2
Components
shows all the components of the RA332 module.
Figure 6: Rear view of the RA332
A
AC or DC power input.
B
Mains and Ready back panel indicators: Mains is lit when the module is powered-
up. Ready indicator lights up after the module self-test is completed.
C
Up to 16 analog inputs for voltage, current, or DC transducers, identified as 101 to
116.