Chapter 15
– Installation
RPV311
RPV311-TM-EN-7
223
The length of the fiber-optic cables shall not exceed 2 km.
Make sure to use the appropriate optical fiber, considering its curvature radius.
For information about optical fiber types and link specifications, see Chapter 17:
Technical Specifications.
When more than one RA333 module is required, an internal module jumper must be
configured, according to the TW link position. The position of links does not have to
be consecutive, but module installation related to A to H position must match the
jumper identification. For example, ID 0 must be the first RA333 (TW) link, ID 1 must be
the second RA333 (TW) link, and so on.
In order to configure these jumpers, remove all connectors and cables which are
connected to the module and remove the back panel of the RA333 removing the 12
screws of the panel and the screw of the protective grounding, as shown in
Figure 113: Screws of the Back Panel
Remove the QTW board, which corresponds to the traveling waves acquisition board.
Configure jumper identification as shown at table 4.1, according to the RA333 TW link
positions.
JP4
JP3
JP2
ID
Open
Open
Open
0
Closed
Open
Open
1
Open
Closed
Open
2
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...