Chapter 6
– Records
RPV311
134
RPV311-TM-EN-7
Figure 71: Example of an event without concatenation
1.5
Trigger Burst Limiter
There is an user-configurable trigger burst limiter for the fault recorder.
The burst limiter is based on the number of triggers time interval (both parameters
are user-configurable). When the limit is exceeded, recording will be disabled for a
period of time defined by the user.
Parameter
Allowed values
Increment
Number of
triggers
0 … 12
1
Time interval
0 … 60 s
1 s
Disabling time
1 … 60 min
1 min
2
Continuous and Trigger'd Disturbance Records
Disturbance records can be created in the following ways:
Continuously: