GE Reason H49
Technical Manual
H49/EN M/C22
123
10.3.3
Safety tests
Description
Test Standard
Test Level
Functional performance requirements
IEC 62439-1:2010
IEC 62439-3:2016
IEC 61850-8-1:2011
IEC 61850-90-4:2013
IEC 61850-9-3:2016
IEC 61588:2009
PRP, HSR and PTP functional features
Clearance and creepage distances
Pollution degree= 2
Overvoltage category = III
IP Rating
IEC 60529: 2013
IP2x for each face
Flammability of insulation materials,
components and fire enclosure
IEC 60695-11-10
UL94V-0
10.3.4
Environmental tests
10.3.4.1
Dielectric
Description
Mode
Group
Test Level
Insulation resistance
Earth and all others Power, Input / output,
Alarm and serial ports
Test voltage 500Vdc
Dielectric type test
Earth and all others AC/DC Power, binary
input/output, alarm ports 2kV - before and after environmental tests
Earth and all others Serial and internet ports 0,5kV - before and after environmental tests
Protective bonding
resistance
Mechanical ports
60s, Test voltage < 12Vdc or 12 Vrms ac
before and after environmental tests
10.3.4.2
Climatic
Description
Test Standard
Test Level
Dry heat - Max operating temp
IEC 60068-2-2:2007
Test Bd: 55°C - 96 hours
Cold - Min operating temp
IEC 60068-2-1:2007
Test Ad: -25°C - 96 hours
Dry heat – Max storage temperature
IEC 60068-2-2:2007
Test Bd: 70°C - 96 hours
Power on @55°C
Cold - Min storage temperature
IEC 60068-2-1:2007
Test Ab: -40°C - 96 hours
Power on @-25°C
Change of temperature
IEC 60068-2-14:2009
Test Nb:
Start = 20°C for 1h
Lower temperature = -25°C
Higher temperature = 55°C
Damp heat - steady state
IEC 60068-2-78:2012
Test Cab:
40°C ±2 °C - RH 93% ± 3% - 10 days