background image

8

DUCT

EQUIVALENT NUMBER

PIECES

LENGTH

x USED

= TOTAL

3

1

4

”x 10”

1 Ft.

x (       )

=

Ft.

Rect., 

straight

7” Round,  1 Ft.

x (       )

=

Ft.

straight

6” Round,  1 Ft.

x (       )

=

Ft.

straight

3

1

4

”x 10”

14 Ft.

x (       )

=

Ft.

Rect. 90° 

elbow

3

1

4

”x 10”

8 Ft.

x (       )

=

Ft.

Rect. 45° 

elbow

3

1

4

”x 10”

33 Ft.

x (       )

=

Ft.

Rect. 90° 

flat elbow

3

1

4

”x 10”

24 Ft.

x (       )

=

Ft.

Rect.

(18 ft. w/o

wall cap

damper)

x (       )

=

Ft.

with 

damper

3

1

4

”x 10”

2 Ft.

x (       )

=

Ft.

Rect. to 

6” round 

transition

3

1

4

”x 10”

4 Ft.

x (       )

=

Ft.

Rect. to 

6” round 

transition 

90° elbow

6” Round, 25 Ft.

x (       )

=

Ft.

90° elbow

6” Round, 16 Ft.

x (       )

=

Ft.

45° elbow

Subtotal column 1

=

Ft.

WORKSHEET—CALCULATE TOTAL EQUIVALENT DUCTWORK LENGTH

DUCT

EQUIVALENT

NUMBER

PIECES

LENGTH

x USED

= TOTAL

6”Round  53 Ft.

x (       )

=

Ft.

wall cap (39 ft. w/o 

with 

damper)

x (       )

=

Ft.

damper

6” Round  72 Ft.

x (       )

=

Ft.

roof cap

6” Round  3 Ft.

x (       )

=

Ft.

to 

3

1

4

”x 10”

rect. 

transition

6” Round  9 Ft.

x (       )

=

Ft.

to 

3

1

4

”x 10”

rect. 

transition 

90° elbow

7” Round,  14 Ft.

x (       )

=

Ft.

90° elbow

7” Round,  9 Ft.

x (       )

=

Ft.

45° elbow

7” Round  28 Ft.

x (       )

=

Ft.

wall cap (21 ft. w/o 

with 

damper)

x (       )

=

Ft.

damper

7” Round  39 Ft.

x (       )

=

Ft.

roof cap

7” Round  1 Ft.

x (       )

=

Ft.

to 

3

1

4

”x 10”

rect. 

transition

7” Round 5 Ft.

x (       )

=

Ft.

to 

3

1

4

”x 10”

rect. 

transition, 

90° elbow

Subtotal column 2

=

Ft.

Subtotal column 1

=

Ft.

Total ductwork

=

Ft.

Installation Instructions

MAXIMUM DUCT LENGTH: For satisfactory air movement,

the total duct length of a 3

1

4

” x 10” rectangular, 7” diameter

round duct 

should not exceed 65 equivalent feet.

1 ft = 0.3 m; 1 in. = 2.5 cm

Summary of Contents for PVWC930

Page 1: ...ovibles Owner s Manual and Installation Instructions PVWC924 PVWC930 PVWS930 PVWG930 PVWT930 S curit 20 21 Utilisation 22 23 Ampoules halog ne 23 Filtre charbon 22 23 Filtre graisses 22 23 Entretien e...

Page 2: ...OBSERVE THE FOLLOWING A Use this unit only in the manner intended by the manufacturer If you have questions contact the manufacturer B Before servicing or cleaning unit switch power off at service pan...

Page 3: ...the fire with your back to an exit aBased on kitchen firesafety tips published by NFPA Proper maintenance of the Range Hood will assure proper performance of the unit WARNING UNDER CERTAIN CIRCUMSTAN...

Page 4: ...ualised on the display until the motor re starts after 50 minutes for another 10 minutes and so on Press any key apart from the light keys to return to normal functioning Press key E to deactivate the...

Page 5: ...ency with which the appliance is used the type of cooking performed and the regularity with which the anti grease filters are cleaned To remove filters refer to Fig 6 Replacing halogen light bulbs Fig...

Page 6: ...n be used to remove embedded dirt Rinse shake and let them dry before replacing They may also be cleaned in an automatic dishwasher NOTE Before cleaning make sure the charcoal filters if present are u...

Page 7: ...RYTE Stainless Steel Cleaning Polish and Conditioner PM10X313 Hood Lights This hood requires two bulbs not included maximum 50 watts Purchase and install WB27M02956 50 W Maximum halogen bulbs When rep...

Page 8: ...ctangular 6 or 7 diameter round duct should not exceed 65 equivalent feet See the WORKSHEET CALCULATE TOTAL EQUIVALENT DUCTWORK LENGTH section NOTE It is important that ducting be installed using the...

Page 9: ...T EQUIVALENT NUMBER PIECES LENGTH x USED TOTAL 6 Round 53 Ft x Ft wall cap 39 ft w o with damper x Ft damper 6 Round 72 Ft x Ft roof cap 6 Round 3 Ft x Ft to 31 4 x 10 rect transition 6 Round 9 Ft x F...

Page 10: ...greater than the width of the range or cooktop but it may not be smaller Ensure the range or cooktop is installed per manufacturer s installation instructions If you are going to vent your range hood...

Page 11: ...ities D Ducted fans must always be vented to the outdoors E This unit must be grounded WARNING TO REDUCE THE RISK OF FIRE USE ONLY METAL DUCTWORK Power Supply Connection For connection to the power su...

Page 12: ...is necessary to install a carrying support structure made by joists from 2 to 4 inches with the points of anchorage of the screws Fixing the decorative telescopic flue Arrange the electrical power su...

Page 13: ...12...

Page 14: ...13 On Some Models...

Page 15: ...14...

Page 16: ...ircuit breaker Fan fails to circulate air or moves air more slowly than normal Excessively soiled filter Wash and replace the filters See the Reusable Metal Grease Filters section Replace the filter i...

Page 17: ...ERSHIP REGISTRATION P O BOX 1780 MISSISSAUGA ONTARIO L4Y 4G1 FOR CANADIAN CONSUMERS ONLY POUR R SIDENTS CANADIENS SEULEMENT Please place in envelope and mail to Veuillez mettre dans une enveloppe et e...

Page 18: ...N O RUE STREET NAME RUE APT NO APP RR CITY VILLE PROVINCE AREA CODE IND R G TELEPHONE T L PHONE E MAIL COURRIEL DID YOU PURCHASE A SERVICE CONTRACT FOR THIS APPLIANCE AVEZ VOUS ACHET UN CONTRAT DE SE...

Page 19: ...ilable you may be responsible for a trip charge or you may be required to bring the product to an Authorized Mabe Service Location for service Some provinces do not allow the exclusion or limitation o...

Page 20: ...Card are accepted Order by phone at 800 661 1616 during normal business hours Instructions contained in this manual cover procedures to be performed by any user Other servicing generally should be ref...

Page 21: ...ces veuillez lire l tiquette des sp cifications situ e sur la hotte AVERTISSEMENT POUR DIMINUER LES RISQUES D INCENDIE DE CHOC LECTRIQUE OU DE BLESSURES VEUILLEZ SUIVRE LES INSTRUCTIONS SUIVANTES A Ce...

Page 22: ...est petit et circonscrit l endroit o il s est d clar 3 Vous avez appel les pompiers 4 Vous pouvez combattre le feu en faisant dos une sortie a Tir du document Kitchen Firesafety Tips Conseils de s cu...

Page 23: ...les heures Lorsque cette fonction est activ e et que la hotte fonctionne le cercle ext rieur de l ic ne tournera sur lui m me sur l afficheur Apr s les 10 minutes de fonctionnement le moteur s teindr...

Page 24: ...rifier l air qui est retourn dans la cuisine Ces filtres ne sont pas lavables ni r utilisables et doivent tre remplac s au moins une fois tous les quatre mois Le niveau de saturation des filtres au ch...

Page 25: ...ttoyage pour four ou abrasifs Vous pouvez effectuer un brossage l ger pour liminer les salet s incrust es Rincez secouez et laissez s cher les filtres avant de les r installer Il est galement possible...

Page 26: ...dable N PM10X313 Lampes de la hotte Cette hotte n cessite l utilisation de deux ampoules non comprises d un maximum de 50 W Achetez et installez des ampoules halog nes WB27M02956 d un maximum de 50 W...

Page 27: ...AGE L vacuation du syst me de ventilation doit se faire vers l ext rieur L vacuation de l air de cette hotte peut se faire verticalement travers les armoires sup rieures ou horizontalement travers un...

Page 28: ...DUIT QUIVALENTE x UTILIS TOTAL vent mural 53 pi x pi rond de 6 po 39 pi sans avec registre x pi registre vent de 72 pi x pi toiture rond de 6 po Adaptateur 3 pi x pi de transition rond de 6 po rect de...

Page 29: ...de cuisson mais elle ne peut pas tre plus petite Assurez vous que la cuisini re ou la surface de cuisson a t install e selon les instructions d installation du fabricant Si l vacuation de l air de vo...

Page 30: ...Lorsque vous effectuez des d coupes ou que vous percez dans un mur ou un plafond n endommagez pas le c blage lectrique ou les installations des services publics D L air des ventilateurs qui disposent...

Page 31: ...install e Installation sur un mur de placopl tre Assurez vous que les vis sont bien fix es aux colombages du mur Si cela n est pas possible vous devrez installer une structure permettant de supporter...

Page 32: ...31...

Page 33: ...32 5 8 po 1 6 cm 10 7 16 po 26 5 cm Sur certains mod les...

Page 34: ...33...

Page 35: ...ir plus lentement qu la normale Les filtres sont tr s encrass s Nettoyez les filtres et remettez les en place Reportez vous la section Filtres graisses m talliques r utilisables Remplacez les filtres...

Page 36: ...35 NOTES...

Page 37: ...r parateur agr par Mabe n est disponible vous devrez peut tre assumer les frais de d placement de celui ci ou apporter le produit un atelier de r paration agr par Mabe Dans certaines provinces il est...

Page 38: ...t es Commandez par t l phone au 1 800 661 1616 pendant les heures normales d ouverture Les instructions contenues dans le pr sent manuel comportent des proc dures que tout utilisateur peut effectuer L...

Reviews: