background image

5

Installation Instructions, Indoor Exhausting

6  ALCOVE OR CLOSET INSTALLATION

7  BATHROOM OR BEDROOM
INSTALLATION

8  MOBILE OR MANUFACTURED
HOME INSTALLATION

If rigid all-metal duct cannot be used, then flexible all-metal ducting 
can be used, but it will reduce the maximum recommended duct 
length. In special installations when it is impossible to use only 
metal ducting, then UL-listed clothes dryer flexible metal transition 
duct may be used as transition venting between the dryer and wall 
connection only. The use of this ducting will affect dry time.

If flexible transition duct is necessary, the following directions 

must

 

     

 

be followed.

• Use the Shortest Length Possible.
• Stretch the Duct to Its Maximum Length to avoid kinks.
• Do Not Crush or Collapse the Duct.
• Never Use Transition Duct Inside the Wall or
  Inside the Dryer.
• Avoid Resting the Duct on Sharp Objects.
• 

Venting Must Conform to Local Building Codes.

              

USING FLEXIBLE METAL DUCTS

• If your dryer is approved for installation in an alcove or 
  closet, it will be stated on a label on the dryer back.
• The dryer MUST be vented to the outdoors. See the 
  EXHAUST INFORMATION sections 3 & 4. 
• Minimum clearance between dryer cabinet and adjacent       
  walls or other surfaces is:

0 in. either side
3 in. front and rear

• Minimum vertical space from floor to overhead cabinets, 
  ceiling, etc. is 52 in.
• Closet doors must be louvered or otherwise ventilated and 
  must contain a minimum of 60 sq. in. of open area equally 
  distributed. If the closet contains both a washer and a 
  dryer, doors must contain a minimum of 120 sq. in. of open 
  area equally distributed.

OTHER INSTALLATIONS: If the installation makes it 
impossible to exhaust to the outdoors, a 4" exhaust 
deflector (WE25X278) must be installed. A clearance of 8" 
is required between the rear of the dryer and the wall, and 
the deflector should be pointing up.

• Installation must conform to the MANUFACTURED 
  HOME CONSTRUCTION & SAFETY STANDARD, 
  TITLE 24, PART 32-80 or, when such standard is not 
  applicable, with AMERICAN NATIONAL STANDARD 
  FOR MOBILE HOME, ANSI/NFPA NO. 501B.
• The dryer MUST be vented to the outdoors with the 
  termination securely fastened to the mobile home 
  structure. (See EXHAUST INFORMATION
  section 3 & 4.)
• The vent MUST NOT be terminated beneath a mobile or 
  manufactured home.
• The vent duct material MUST BE METAL.
• Do not use sheet metal screws or other fastening  devices 
  which extend into the interior of the exhaust vent.
• See section 2 for electrical connection information.

INDOOR EXHAUSTING

NOTE: MOBILE HOME, BEDROOM, BATHROOM,
ALCOVE OR CLOSET INSTALLATIONS
MUST BE EXHAUSTED TO THE OUTDOORS

NOTE: EXHAUSTING TO THE OUTDOORS IS
STRONGLY RECOMMENDED, EXHAUSTING
INDOORS MAY CAUSE LINT ACCUMULATION,
AND MOISTURE DAMAGE INCLUDING MOLD
AND MILDEW.

ELBOWS HIGHLY
RECOMMENDED

ELBOW HIGHLY
RECOMMENDED

DO NOT
SIT DRYER
ON FLEXIBLE
EXHAUST.

DO NOT USE
EXCESSIVE
EXHAUST
LENGTH

DO NOT
CRUSH
FLEXIBLE
EXHAUST
AGAINST
WALL.

DO

DON’T

• The dryer MUST be vented to the outdoors. See 
  EXHAUST INFORMATION section 3 & 4.
• The installation must conform with local codes or, in the 
  absence of local codes, with the NATIONAL  ELECTRI-     
  CAL CODE, ANSI/NFPA NO. 70.

ELBOWS HIGHLY
RECOMMENDED

ELBOW HIGHLY
RECOMMENDED

DO

DO

Reviews: