OPM_GTU_19X_1K0_3K0_XUS_V014

 

10

 

GT-UL Series: User manual 1.2 (US)

 

Digital Energy

 

GT Series

g

 

 

 

 

 

3.1 Operation 

Panel 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Switch ‘I/TEST’ 

- Switches on the UPS 
- In ‘ON-LINE’ mode it starts the battery test 
- In ‘ON BATTERY’ mode it mutes the buzzer 

 

 

 

Off switch 

Switches off the UPS 

 

 

 

LED ‘Bypass’ 

The UPS is in ‘BYPASS’ mode: the incoming utility power is 
channeled directly to the load. See also 3.3.5 

 

 

 

LED ‘Line’ 

Indicates the condition of the utility input power.  

Continuously

 lighting up: the input power is OK, 

Flashing

: input voltage is too low, too high, or out of frequency, 

Off

: blackout or ultra high voltage (>150Vac) 

 

 

 

LED ‘On Line’ 

The UPS is operating in the (normal) ‘ON LINE’ mode 

 

 

 

LED ‘On Battery’ 

The UPS is operating in ‘ON BATTERY’ (back-up) mode: utility 
power fails, and the internal batteries supply the required 
power until either they are depleted or utility power returns. 

 

 

 

Level bar 

- In ‘ON BATTERY’ mode: shows current battery capacity 
- In ‘ON LINE’ mode: showing current load level 

 

 

 

Battery LED 

Level bar shows current battery capacity 

 

 

 

Load LED 

Level bar shows current load level 

 

 

 

10 

Battery low LED 

The battery is almost depleted 

 

 

 

11 

Replace battery LED 

After a battery test the LED shows that the batteries are weak. 
Battery replacement is recommended 

 

 

 

12 

Overload LED 

The load exceeds the nominal UPS rating. After a short period 
of time the UPS will transfer to ‘BYPASS’ mode 

 

 

 

13 

Fault LED 

The UPS is faulty 

 
 

Fig. 3.1  Operating panel

3  -  Operation

 

1

2

7

3

5

13

12

11

10

Summary of Contents for Power Supply

Page 1: ...ower Supply 1000 1500 3000 VA UL version GE Consumer and Industrial Power Quality Digital Energy 701 E 22nd Street Suite 300 Telephone 800 637 1738 Lombard IL 60148 USA Website www geindustrial com up...

Page 2: ...power failures Please keep this manual in a safe place for future reference and carefully read the important safety instructions in chapter 1 before installation and start up of the UPS 2007 by GE Co...

Page 3: ...er available 3 2 2 Start up utility power not available cold start or battery start 3 3 Use Normal Operation 3 3 1 Normal operation conditions 3 3 2 Normal operation indications 3 3 3 UPS self test 3...

Page 4: ...ing maintenance or service work The UPS contains potentially hazardous voltages 1 3 Installation The unit should be installed by service personnel To reduce the risk of electric shock install this UPS...

Page 5: ...t charging source prior to connecting or disconnecting battery terminals Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground Contact with any part of a...

Page 6: ...nterface cables when connecting to computer or peripheral devices Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate...

Page 7: ...UPS 4 Output circuit breaker Protects the UPS from damage caused by output overload 5 DC connector To connect external battery pack for extended runtime 6 Fan Electronically controlled cooling fan Ma...

Page 8: ...r of the UPS indicated on the rating label 2 4 1 Mounting in a 19 enclosure 1 Install the mounting bracket See fig 2 2 2 Adjust the rails and gently slide UPS into the rails See fig 2 3 3 Fix mounting...

Page 9: ...RS232 dry contact interface Connect the interface signal cable between the RS 232 dry contact port on the rear panel of UPS and COM1 or COM2 of your computer if necessary See fig 2 6 Refer to chapter...

Page 10: ...batteries the internal energy reserve were fully charged when the UPS left the factory they might have lost some energy during transport and or storage It is recommended to allow the UPS to recharge...

Page 11: ...ting in the normal ON LINE mode 6 LED On Battery The UPS is operating in ON BATTERY back up mode utility power fails and the internal batteries supply the required power until either they are depleted...

Page 12: ...ges the batteries 3 3 Use Normal Operation 3 3 1 Normal operation conditions The utility power supply is present and within allowable tolerances The load does not exceed the nominal rating of the UPS...

Page 13: ...beeps with a 2 seconds interval When the utility power returns the UPS will switch back to normal operation In case of a long power failure the UPS will stop operating when the batteries have been dep...

Page 14: ...the UPS functions under overload or over temperature conditions it may not be able to protect the load 3 4 5 Replace battery The batteries are aged and must be replaced as soon as possible to ensure...

Page 15: ...or need a special UPS monitoring software For specific information on GE Digital Energy connectivity products please contact your local dealer 1 800 637 1738 The dry contacts 4 3 and optional SNMP plu...

Page 16: ...at Hardware Baud rate 2400 bps Data length 8 bits Stop bit 1 bit Parity none Cabling Standard sub D 9 cable UPS side male PC side female 4 3 Dry Contact Its major functions are some or all of the foll...

Page 17: ...otocol you can use browser Microsoft IE or Netscape Communicator to monitor or configure the UPS Besides the SNMP card supports Telnet and FTP for remote monitoring and firmware upgrading Specificatio...

Page 18: ...teries General The service life of the battery is from 3 to 6 years depending on the operating conditions mainly temperature and number of discharge cycles As a healthy battery is critical to the perf...

Page 19: ...4 Unscrew two bolts 5 6 Remove stop holder and battery terminal 7 Grasp the tag to pull out the battery sets Be careful heavy weight Notice not to let the battery set to drop in accident 7 When you s...

Page 20: ...ow UPS to cool down Utility failure battery depleted Wait until utility power returns Input breaker tripped See above LED Fault lights up buzzer sounds continuously Internal UPS failure Contact your d...

Page 21: ...ins Battery Recharge Time 4 6 hours after complete discharge to recover 90 Transfer Time Transfer Time zero LED Status On line Bypass On battery Overload Battery Low Fault Battery Replace Battery Leve...

Reviews: