GE PI6000 - Sentrol Motion Detector Installation Instructions Download Page 2

 6000 Series PIR

Installing the Detector

1.

Select an appropriate mounting location.

2.

Route wiring to the detector’s location.

3.

Open the detector and, after selecting appropriate mounting and
wire entry options, remove the knockouts by depressing from the
inside of the detector in the center of desired knockout (see Figure
3). The circuit board may be removed to facilitate mounting and
removal of knockouts if desired.

CAUTION

You must be free of all electricity before handling sensor circuit
boards. Touch a grounded bare metal surface before touching
circuit boards or wear a grounding strap. Promptly reinstall the
circuit board when finished with knockout removal and mounting
the back housing.

4.

Pull cable through the appropriate knockout and fasten the
detector to the wall.

5.

Strip back the outer jacket and individual wires of the cable and
connect the conductors to the proper terminals (see Figure 4). The
alarm contacts are not polarity sensitive.

Note

Use caution not to strip more insulation than needed, approxi-
mately 1/4” (0.6cm), so that bare wires do not touch and cause a
short.

6.

Route the cable through the strain relief located on the far left side
of the back housing (see Figure 3). Snap on the front housing.

7.

Walk test the detector and check for desired coverage.

Note

Most units walk test more accurately if the person testing waits
10 seconds between tripping the unit and walking again. This
allows the detector to stabilize between trips.

Mounting Height Settings

The factory setting of the detector is for mounting heights of 7 to 8 feet
(2.1 to 2.4m). For this setting, the locking tab on the back housing is in
the notch by the 7-8’ arrow on the circuit board (position A in Figure 4).

For proper operation at mounting heights above 8 feet (2.4m), the locking
tab must be in the notch by the 8-9’ arrow (position B in Figure 4).

Figure 4 . Circuit Board

Power In

10 to 16 VDC

T

       

T

+

       

     

NC

  

COM

3

2

8/9'

7/8'

PET

J4

 

LED

J3

PULS

E

A

B

Jumpers

J3 J4

Figure 3.  Back Housing

Wire entry hole for

surface wire runs

Primary wire entry

hole for corner

Primary mounting hole

for flat wall mounting

Locking tab

Center  wire

entry hole

Cable strain

relief

Additional wire entry hole

Secondary mounting hole

used to lock down when flat

wall mounting

Mounting

holes for

corner

mounting

Setting the Jumpers

J3 Pulse Count -

ON = Three-pulse mode

OFF = Two-pulse mode  (factory default)

Note

Use two-pulse mode for all residential
applications including pet applications.

J4 LED -

ON = LED enabled (factory default)

OFF = LED disabled

Pet Applications

A. For pet applications, the detector should be installed at the standard
7 to 8 feet (2.1 to 2.4m) mounting height. Verify that the circuit board is
properly positioned in the back housing (see Mounting Height Settings).

B. Place the pulse count selection jumper in two-pulse mode (see
Setting the Jumpers).

C. Make sure animals cannot get within 6 feet (1.8m) of the detector’s
line of sight or climb on furniture within 6 feet (1.8m) of the detector.

Note

False alarm immunity from any number of small pets and rodents
can be expected as long as the total combined weight does not
exceed 30 lbs. and room temperature does not fall below 50° F
(10° C).

Long Hair

Short  Hair

Not Recommmended

Up to 50 lbs

Up to 30 lbs

Cocker Spaniel

Basenji

Doberman

Eskimo

Border Terrier

Greyhound

Husky

French Bulldog

Mastiff

Pekinese

Welsh Corgi

Shepherd

Sheepdog

Cats

St. Bernard

The pet immunity feature has not been tested by Underwriters
Laboratories Inc.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for PI6000 - Sentrol Motion Detector

Page 1: ...r at a height of 7 to 9 feet 2 1 to 2 7m See Mounting Height Settings Mount the detector either flat on the wall or in a corner and at least 3 8 0 95cm from the ceiling See Figure 2 Do not locate the detector where it may be exposed to false alarm sources such as heat sources in the field of view direct or reflected sunlight strong air drafts fans air conditioners etc on unit Do not aim the detect...

Page 2: ...the circuit board position A in Figure 4 For proper operation at mounting heights above 8 feet 2 4m the locking tab must be in the notch by the 8 9 arrow position B in Figure 4 Figure 4 Circuit Board Power In 10 to 16 VDC T T NC COM 3 2 8 9 7 8 PET J4 LED J3 PULSE A B Jumpers J3 J4 Figure 3 Back Housing Wire entry hole for surface wire runs Primary wire entry hole for corner Primary mounting hole ...

Page 3: ... press it onto the corresponding grooved segment on the lens 4 Reinstall the lens in the front housing The notch on the lens matches the notch on the front housing bottom right corner 5 Snap the shield assembly back into the front cover Maintaining the Detector When installed and used properly the detectors provide up to 5 years of service with minimal maintenance To ensure proper operation walk t...

Page 4: ...ng Flat wall or corner Dimensions Width 3 05 7 75cm Depth 1 90 4 83cm Height 2 68 6 81cm Color White USA Canada 800 547 2556 Technical Service 800 648 7424 FaxBack 800 483 2495 wm GE Security 12345 SW Leveton Drive Tualatin OR 97062 Phone 503 692 4052 Figure 7 Dimensions Front View Side View 2 68 6 81cm 3 05 7 75cm 1 90 4 83cm The unit should be connected to a UL Listed power supply or control uni...

Reviews: