background image

20

49-5000765  Rev. 1

Additional Information

Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all 
its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried 
out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It 
is essential that electrical power is available before the task is commenced.

a) Become familiar with the equipment and its operation. 
b) Isolate system electrically. 
c) Before attempting the procedure, ensure that:

• mechanical handling equipment is available, if required, for handling refrigerant cylinders; 
• all personal protective equipment is available and being used correctly; 
• the recovery process is supervised at all times by a competent person; 
• recovery equipment and cylinders conform to the appropriate standards.

d) Pump down refrigerant system, if possible. 
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. 
f) Make sure that cylinder is situated on the scales before recovery takes place. 
g) Start the recovery machine and operate in accordance with manufacturer’s instructions. 
h) Do not overfill cylinders. (No more than 80 % volume liquid charge). 
i) Do not exceed the maximum working pressure of the cylinder, even temporarily. 

M:KHQWKHF\OLQGHUVKDYHEHHQILOOHGFRUUHFWO\DQGWKHSURFHVVFRPSOHWHGPDNHVXUHWKDWWKHF\OLQGHUV

 

   and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. 
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned 
    and checked.

Labelling

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be 
dated and signed. For appliances containing 

FLAMMABLE REFRIGERANTS

, ensure that there are labels on the 

equipment stating the equipment contains flammable refrigerant.

Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice 
that all refrigerants are removed safely.When transferring refrigerant into cylinders, ensure that only appropriate 
refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total 
system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure-
relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, 
if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set 
of instructions concerning the equipment that is at hand and shall be suitable for the recovery of all appropriate 
refrigerants including, when applicable, 

FLAMMABLE REFRIGERANTS

. In addition, a set of calibrated weighing 

scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings 
and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been 
properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a 
refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant 
supplier in the correct recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in 
recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that 
they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within 
the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only 
electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a 
system, it shall be carried out safely.

ADDITIONAL

 INFORMA

T

ION

Summary of Contents for PHNT12

Page 1: ...ONER ROOM 49 5000765 Rev 1 04 23 GEA SAFETY INFORMATION 3 OPERATING INSTRUCTIONS 5 CARE AND CLEANING 8 INSTALLATION INSTRUCTIONS 9 TROUBLESHOOTING TIPS 16 WIFI SETUP 18 LIMITED WARRANTY 21 CONSUMER SU...

Page 2: ...s into every GE Appliances product and we think you will too Among other things registration of your appliance ensures that we can deliver important product information and warranty details when you n...

Page 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Page 4: ...y a qualified electrician to make sure the outlet is properly grounded Where a 2 prong wall outlet is encountered it is your personal responsibility and obligation to have it replaced with a properly...

Page 5: ...ncrease Decrease pads will set the timer in 1 hour intervals To review the remaining time on the Delay timer press the Delay SDG 8VH WKH Increase Decrease pads to set a new time if desired To cancel t...

Page 6: ...d off with the compressor This may result in wider variations of room temperature NOTE the fan may continue to run for a short time or may pulse intermittently after the compressor cycles off to sampl...

Page 7: ...of collecting water under the unit before removing the plug Locate the drain cap on the right side of the unit Remove the cap and pull the plug straight out CAUTION DO NOT operate the air conditioner...

Page 8: ...QRW PL ROG DQG QHZ EDWWHULHV R QRW PL VWDQGDUG carbon zinc or rechargeable ni cad ni mh etc batteries Draining the Unit Over time the air conditioner will accumulate water on both the indoor and the o...

Page 9: ...service technician Phillips head screwdriver Ruler or tape measure Pencil Level Scissors or knife UNPACKING THE AIR CONDITIONER WARNING EXCESSIVE WEIGHT HAZARD When moving or lifting the air conditio...

Page 10: ...Sash Lock 1 Air Conditioner 1 Power Speed Mode Quiet Delay Remote Control 1 Foam Spacer 1 only needed if ZLQGRZ VLOO WULP GRHV QRW VWLFN RXW Cut to size Foam Side Panel 1 Foam Mounting Support 2 Side...

Page 11: ...must be within reach of the power cord Follow the dimensions in the table and illustration for your model Avoid blocking the vents on the back of the indoor VLGH RI WKH XQLW 7KHUH PXVW EH D 0 1 080 JD...

Page 12: ...Place tab of side panel bracket into slot on chase way to hold position Install the 4 screws 2 on each side back into place to lock in chase way Locking Screws 4 PULL PULL 3 WALL REQUIREMENTS Measure...

Page 13: ...areas made by the DGMXVWPHQW Apply one piece on the left and one piece on the right 5 INSTALL UNIT IN WINDOW Lift the unit into and over the window Center the unit on the Foam Mounting Supports It is...

Page 14: ...cil After laying the foam down close the window on top of it Adhesive Weather Stripping Foam 6 INSTALLING SIDE FILLER PANELS cont Attaching Side Panels cont Measure the gaps from the side of the unit...

Page 15: ...on below B To provide additional security a Sash Lock is provided Attach the Sash Lock to the window VLGH MDPE ZLWK RQH 7 SH VFUHZ C Stuff the Foam Top Window Gasket between the glass and the window t...

Page 16: ...furniture blocking the vents on the front bottom and back of the air conditioner The temp control may not be set correctly On models with touch pads In the Cool mode press the Decrease pad On models w...

Page 17: ...Water Plug is properly inserted This plug may be removed during operation to minimize water in the back of the unit however removing it will lower the efficiency of your unit DWHU GURSOHWV EHLQJ WKURZ...

Page 18: ...is held in strict accordance with the GE Appliances Connected Data Privacy Policy Visit geappliances com privacy privacy_policy_connected to view this policy How it Works Download the GE Appliances Ap...

Page 19: ...ns However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determine...

Page 20: ...quipment stating the equipment contains flammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refriger...

Page 21: ...onnecting facilities Failure of the product resulting from modifications to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance Replacement of hous...

Page 22: ...WHULDO Q WKH 86 GEAppliances com register Parts and Accessories Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes VISA MasterCard and Dis...

Page 23: ...cencia de marca Escriba los n meros de modelo y de serie aqu N de Modelo ____________ N de Serie ______________ Estos n meros se encuentran en una etiqueta al costado del acondicionador de aire PHNT10...

Page 24: ...y creemos que usted tambi n Entre otras cosas el registro de su electrodom stico asegura que podamos entregarle informaci n importante del producto y detalles de la garant a cuando los necesite Regis...

Page 25: ...LQ GH DVHJXUDU TXH no se juegue con el electrodom stico 1R XWLOLFH VX DFRQGLFLRQDGRU GH DLUH HQ XQD KDELWDFLyQ h meda tal como un ba o o lavadero O HOHFWURGRPpVWLFR VH GHEHUi JXDUGDU D ILQ GH HYLWDU T...

Page 26: ...para asegurar que el enchufe est correctamente conectado a tierra En caso de contar con un tomacorriente de pared de 2 cables es su responsabilidad y obligaci n reemplazarlo por un tomacorriente de p...

Page 27: ...1 y 24 horas C mo configurar 3UHVLRQH OD WHFOD HOD 5HWUDVR DGD YH TXH VH presionen las teclas se configurar el temporizador en intervalos de 1 hora Para revisar el tiempo restante del temporizador de...

Page 28: ...iaciones mayores en la temperatura de la habitaci n NOTA es posible que el ventilador contin e funcionando durante un per odo de tiempo corto o que titile de forma intermitente cuando el compresor fin...

Page 29: ...etirar la tapa sin embargo se comenzar a drenar tan pronto como el Filtro del Tap n sea retirado Aseg rese de contar con los medios adecuados para recolectar agua debajo de la unidad antes de retirar...

Page 30: ...DV HVWiQGDU FDUERQR FLQF RUHFDUJDEOHV QL FDG QL PK HWF Drenaje de la Unidad Con el paso del tiempo el acondicionador de aire acumular agua tanto del lado interior como del exterior Por diversas razone...

Page 31: ...AIRE ACONDICIONADO WARNING PELIGRO DE PESO EXCESIVO cuando mueva o levante el aire acondicionado utilice GRV R PiV SHUVRQDV 8VH JXDQWHV FXDQGR PDQLSXOH HO acondicionador de aire para protegerse contr...

Page 32: ...Speed Mode Quiet Delay RQWURO 5HPRWR 3DQHO DWHUDO GH RPDHVSXPD FRUWDGR D PHGLGD Soporte del Panel DWHUDO Junta Superior de Ventana de RPDHVSXPD Gomaespuma del Burlete Adhesivo FRUWDGD D PHGLGD Soport...

Page 33: ...ventana Height Ancho Ancho Altura M n Altura M n desde el Piso 2 PREPARE EL ACONDICIONADOR DE AIRE Mida el ancho de la abertura de la ventana y marque el centro de la abertura de la ventana Centre el...

Page 34: ...en la ranura de la ruta del cableado para sostener la posici n 9XHOYD D LQVWDODU ORV WRUQLOORV D FDGD ODGR HQ VX posici n para bloquear la ruta del cableado Tornillos de ORTXHR PULL PULL 3 REQUISITOS...

Page 35: ...frontales est n alineados con la l nea dibujada como se observa a continuaci n 5 INSTALE LA UNIDAD EN LA VENTANA HYDQWH OD XQLGDG GHQWUR VREUH OD YHQWDQD Centre la unidad sobre los Soporte de Montaje...

Page 36: ...a del Burlete Adhesivo 6 INSTALE LOS PANELES DE RELLENO LATERALES cont Adhiera los Paneles Laterales cont Mida las brechas desde el lateral de la unidad hasta los extremos de la ventana y corte los Pa...

Page 37: ...estra a continuaci n B A fin de contar con seguridad adicional se brinda un Bloqueo del Marco Adhiera el Bloqueo del Marco a la jamba lateral de la ventana con un tornillo Tipo B C Coloque la Junta Su...

Page 38: ...tinas persianas ni muebles que bloqueen las ventilaciones sobre el frente la parte inferior y la parte trasera del acondicionador de aire El control de temperatura no est ajustado apropiadamente Q ORV...

Page 39: ...de la Sub base de goma se encuentre insertado de forma correcta Este tap n se podr retirar durante el funcionamiento para minimizar la cantidad de agua en la parte trasera de la unidad sin embargo su...

Page 40: ...V HQ HVWULFWR FXPSOLPLHQWR FRQ OD 3ROtWLFD GH 3ULYDFLGDG GH DWRV GH RQH LyQ GH SSOLDQFHV 3DUD DFFHGHU D HVWD SROtWLFD visite geappliances com privacy privacy_policy_connected CONFIGURACI N WIFI C mo F...

Page 41: ...en una instalaci n en particular Si este equipo provoca interferencias perjudiciales para la recepci n de radio o televisi n lo que puede comprobar encendiendo y apagando el equipo se aconseja al usua...

Page 42: ...mismo contiene refrigerante inflamable Recuperaci n Al retirar el refrigerante de un sistema ya sea para realizar el servicio t cnico o para su desensamble se recomienda como una buena pr ctica que to...

Page 43: ...apacidad adecuada contacte a su vendedor minorista o instalador Usted es responsable de brindar instalaciones de conexi n el ctrica adecuadas DOOD GHO SURGXFWR FRPR UHVXOWDGR GH PRGLILFDFLRQHV VREUH e...

Page 44: ...GEAppliances com register Piezas y Accesorios Aquellos individuos calificados para realizar el servicio t cnico de sus propios electrodom sticos podr n solicitar el env o de SLH DV R DFFHVRULRV GLUHFW...

Reviews: