PanaFlow™ XMT1000 User’s Manual
65
Appendix D. Foundation Fieldbus Communication
D.4.2 Password (cont.)
To
Edit
the fields in the
Transducer Blocks
, complete the following steps:
1.
Select or enter the
new value
.
2.
Click on the
Write Changes
button.
3.
Return to the
Resource Block > Others
tab and select
Commit
from the
SYTEM_REQ_COM
drop down box
4.
Click on the
Write Changes
button.
To
Exit
configuration mode, complete the following steps:
1.
Select
Cancel
from the
SYSTEM_REQ_CMD
drop down box.
2.
Click on the
Write Changes
button.
Note:
The XMT1000 will automatically exit configuration mode after 5 minutes of inactivity.
D.4.3 NAMUR NE107
The
NAMUR NE107
recommendation specifies that detailed device-specific diagnostics are summarized as four simple
status signals. The diagnostics are set to defaults by GE, but they can be modified to any other level by the user. The
four status signals are:
•
Failed:
This category is typically used for hardware or software failures. The meter output is not valid. Consult
with the factory for a resolution.
•
Offspec:
This category is typically used for application, installation, or process problems. Consult the
troubleshooting section of this appendix or contact GE customer service for assistance.
•
Check:
This category means the output of the device is invalid due to on-going work on the device, such as
programming, etc.
•
Maintenance:
This category is typically used to assign parameters that are in good status but which may fall
out of specification due to some process condition or wear factor. There are no diagnostics set as default in this
category.
The status signals (see
below) can either be reported as errors (
ACTIVE
) or masked when the error occurs
(
MASK
). There are no default settings for the
MASK
bits.
Figure 26: NAMUR NE107 Configuration in Resource Block
Summary of Contents for PanaFlow XMT1000
Page 1: ...GE Oil Gas Flow 910 313 Rev A June 2017 PanaFlow XMT1000 User s Manual ...
Page 2: ......
Page 4: ...ii no content intended for this page ...
Page 8: ...Contents vi PanaFlow XMT1000 User s Manual no content intended for this page ...
Page 12: ...Preface x PanaFlow XMT1000 User s Manual no content intended for this page ...
Page 46: ...34 PanaFlow XMT1000 User s Manual no content intended for this page ...
Page 95: ......