GE PACSystems* RX3i Important Product Information Download Page 2

2

 

 

IC695ACC400 

GFK-2724A 

 

Installation 

The Energy Pack is mounted on the left side of an RX3i module. To avoid taking up a backplane slot, it should be mounted 
on the module (usually a power supply) in slot 0 of the rack. It is connected to the CPU by cable IC695CBL001. 
Note that, when mounted on a module in slot 0, the Energy Pack will extend approximately 13mm (0.5") beyond the left 
side of the backplane. 
To install the Energy Pack: 

1.

 

Engage the top mounting hooks on the frame of the Energy Pack module as shown in Figure 3. 

2.

 

Rotate the bottom of the Energy Pack into place, engaging the bottom hooks. The latch will snap into place. 

3.

 

Connect the IC695CBL001 cable from the connector on the bottom of the Energy Pack (Figure 2) to the 
corresponding connector on the bottom of the CPU. 

 

 

Figure 2: ACC400 

Bottom View 

 

 

POWER 

P/S FAULT 

OVERTEMP 

OVERLOAD 

Power Supply 

40W AC 

 

 

PACSystems 
RX3i 

 

Figure 3: Installation of ACC400 Energy Pack: Connect to CPU via Cable IC695CBL001 

 