3.4.
PROFINET Controller Configuration
PROFICY Machine Edition 8.60 SIM 13, PME 9.00 SIM 4 or later may be used to
configure an Embedded PROFINET Controller in the CPE330 Hardware Configuration
on LAN 2. To enable the PROFINET Controller in a CPE330 project, select the CPE330
target in the
PME Navigator
and open the Hardware Configuration. On the
Settings
tab, change the
LAN 2 Mode
to
PROFINET
. The
PROFINET Controller
node description
now displays that it is using LAN 2 as a submodule under the CPE330.
3.5.
Backward Compatibility with CPU320/CRU320/CPU315
The CPE330 also serves as a drop-in replacement for the CPU320, CRU320, and
CPU315 Controllers without the need to upgrade PME. To download projects intended
for the CPU320/CRU320 to a CPE330 with versions of PME that do not support the
CPE330, you must change the CPE330’s compatibility setting. To change the
compatibility setting, perform the following operations:
1.
Power off the CPE330 and remove any USB stick that might be attached to
its USB connector.
2.
Place the CPE330’s RUN/STOP switch in the STOP position.
3.
Hold down the RDSD UPLD button and turn power on to the CPE330.
Continue to depress the RDSD UPLD button until the CPE330 powers up and
displays one of the following patterns on the LEDs.
13
PACSystems* RX3i 1GHz 64MB CPU w/Ethernet Quick Start Guide
GFK-2941E