background image

NX-148E-RF LCD Touchpad with Receiver

Installation Instructions

4

Transmitter options

Door/window transmitter settings

To set features 4 (Input option 1) and 5 (Input option 2) for door/
window transmitters, do the following:

• To disable the transmitter’s internal reed switches, turn on 

feature 4.

• Turn on feature 5 for a normally closed (N/C) external 

contact; turn off feature 5 for a normally open (N/O) 
external contact.

Wireless smoke detector settings

To set feature 4 (Input option 1) for wireless smoke detectors, do 
the following:

• For wireless smoke detectors with tamper switches, turn 

feature 4 on to enable the tamper feature. 

• For wireless smoke detectors without tamper switches, turn 

feature 4 off (disabled).

Note:  

Feature 4 must be off (disabled) when using wireless smoke 
detectors without tamper switches.

4-button keyfob settings

Keyfob functions 1 and 2 can be used to control relays, outputs, 
or X10 devices. See Locations 593 and 594 in 

Table 11 

on 

page 10.
To set features 4 (Input option 1) and 5 (Input option 2) for 4-

button keyfobs, do the following:

• To change the Light button to keyfob function 1, turn on 

feature 4.

• To change the Star button to keyfob function 2, turn on 

feature 5.

Partition settings for keyfobs

To program partition settings, do the following:
1.

Enter 

* 8

 at the touchpad.

2.

Enter your program code (factory default is 9 7 1 3). 

3.

Enter the device number and press 

#

 (see 

Table 2 

on 

page 3).

4.

Enter the location number and press 

#

. For example, enter 

401 #

 to enter location 401, segment 1. Press * for segment 2. 

5.

Press the touchpad button that corresponds to the keyfob 

partition number you want to change. The number will be 
displayed for the keyfob partitions. Press the partition 
number to toggle the partition on and off.

6.

To continue programming keyfob transmitter partition 

settings, repeat steps 4 to 8.

7.

To exit program mode, press 

EXIT EXIT

.

Transmitter supervision windows

To change the transmitter supervision windows, do the 
following:
1.

Enter 

* 8

 at the touchpad.

2.

Enter your program code (factory default is 9 7 1 3). 

3.

Enter the device number and press 

(see 

Table 2 

on 

page 3).

4.

Enter 

595 #

 to enter location 595, segment 1.

5.

Enter the new normal supervision time (0 to 255) and press 

*

. If you enter 0, it will set the normal supervision time to 

256 hours. 

6.

Enter the new fire supervision time (0 to 255) and press 

*

. If 

you enter 0, it will set the fire supervision window to 256 
hours.

7.

Enter the new short supervision time (up to 30 minutes). 
The short supervision setting prevents arming if a trans-

mitter has not checked in within the set time. This applies 
only to specific countries outside the U.S. Check the control 
panel installation manual to determine if this setting is avail-

able. Enter a number higher than 30 (the default value is 40) 
to disable the feature.

8.

Press 

*

 to save any changes. The panel is now waiting for 

the next location entry.

Note:  

If you press 

it does not save changes to the current 

segment, but it does save changes made in previous 
segments.

9.

To exit program mode, press 

EXIT EXIT

.

Delete transmitters

This procedure makes the receiver ignore a transmitter but does 
not remove transmitter identification from the receiver’s 

memory. The transmitter can be reactivated later or a new one 
can be learned into the zone.
To delete a transmitter, do the following:
1.

Enter 

* 8

 at the touchpad.

2.

Enter your program code (factory default is 9 7 1 3).

3.

Enter the device number and press 

(see 

Table 2 

on page 3). 

4.

Enter the zone location and press 

#

. For example, enter 

407 

#

 to delete zone 7. 

5.

To change transmitter feature 1 (

Transmitter enabled

), enter 

and press 

*

. The 1 turns off to indicate the feature change.

6.

To delete additional transmitters, repeat steps 3 to 5.

Note:  

To delete all transmitters and load factory defaults, 
enter 910 #.

7.

To exit program mode, press 

EXIT EXIT

.

Transmitter testing and troubleshooting 

Test all transmitters to verify correct programming and operation. 
Location 600 gives the number of rounds of the last transmitter 

learned in. A minimum of 7 to 8 transmissions is required for all 
transmitters. If the number of transmissions is less than the 
minimum required, supervisories can occur.
Rotate the mounting position (90, 180, or 270 degrees) of any 
transmitter that consistently tests below margin and retest.
If rotating the transmitter mounting position does not improve 

signal reception or is not practical, move the transmitter to 
different locations near the preferred mounting area. Test each 
location until the transmitter consistently tests good, then mount 

the transmitter.

CAUTION:  

Do not set the normal or fire supervision 
windows to 1 hour. This causes false 
trouble reports from all learned wireless 
transmitters.

Summary of Contents for NX-148E-RF - Security NetworX NX-8E System

Page 1: ... Phillips screwdriver Drill 15 64 in drill bit Mounting screws provided Wall anchors optional 4 conductor 22 18 16 14 or 12 gauge wire see Table 1 on page 2 Installation To install the touchpad do the following 1 Remove the mounting plate screw Figure 1 from the bottom of the touchpad and lift off the mounting plate 2 At the mounting location use the mounting plate to mark the location for the ant...

Page 2: ...t overlap any blocks of 8 zones All other control panels can have wireless zones added to any zone If a hardwire input on either the control panel or hardwire expander is also present on the same zone as an enabled wireless zone the wireless transmitter takes priority Program settings When programming wireless transmitters into the touchpad there are various options and partitions you can set for ...

Page 3: ...irmation 9 To program remaining transmitters repeat steps 6 to 8 10 To exit program mode press EXIT EXIT Table 2 Device numbers Partition Touchpad 1 2 3 4 5 6 7 8 1 192 193 194 195 196 197 198 199 2 200 201 202 203 204 205 206 207 3 208 209 210 211 212 213 214 215 4 216 217 218 219 220 221 222 223 5 224 225 226 227 228 229 230 231 6 232 233 234 235 236 237 238 239 7 240 241 242 243 244 245 246 247...

Page 4: ...l supervision time to 256 hours 6 Enter the new fire supervision time 0 to 255 and press If you enter 0 it will set the fire supervision window to 256 hours 7 Enter the new short supervision time up to 30 minutes The short supervision setting prevents arming if a trans mitter has not checked in within the set time This applies only to specific countries outside the U S Check the control panel inst...

Page 5: ...if the system requires service To access the service menu do the following 1 Enter 2 to display one or more of the fault messages in Table 9 on page 8 2 Press or to scroll through the messages 3 To exit the service messages press View alarm memory 3 To view alarm memory do the following 1 Enter 3 2 Press or to display the alarm memory list in sequential order by zone number 3 To exit press Test fu...

Page 6: ... Enter 6 2 Enter your master code 3 Enter the user number 4 Use keys 1 yes and 0 no to assign authorities when prompted or press to move to the next prompt 5 Assign the partitions for the user 6 To return to step 3 and program another user code press 7 To exit press Note Retain at least one code with access rights to all partitions to allow adding future users Reset function 7 The system must be d...

Page 7: ...Enter your program code 3 Enter the elapsed time in minutes using three digits For example enter 005 for 5 minutes 4 To exit press Set system time and date 97 To set the system time and date do the following 1 Enter 97 2 Enter your program code 3 Press or to scroll for the proper hour 4 Press to advance to the next selection minutes 5 Repeat steps 3 and 4 until the time and date are set 6 To exit ...

Page 8: ...s not operating properly Control fail to comm The control made an unsuccessful attempt to communicate a message to the central station Control ground fault A short to ground has been detected on a control circuit Control loss of time Your system has lost total power and needs the clock reset Control power trouble The main power to the system is off Control low battery The standby battery is low Ex...

Page 9: ...tor test at a specified interval Start Prog Start programming Local Programming has started End Prog End programming Local programming has ended Start Dnld Start download Download session has started End Dnld End download Download session has ended Cancel Cancel was initiated within 5 minutes of an alarm Gnd Flt Ground fault A short to ground has been detected Man Test Manual test Bell and or comm...

Page 10: ...eyfob Partition 5 keyfob Partition 6 keyfob Partition 7 keyfob Partition 8 keyfob Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4 Input option 1 5 Input option 2 _ 6 8 Not used Partition 1 keyfob Partition 2 keyfob Partition 3 keyfob Partition 4 keyfob Partition 5 keyfob Partition 6 keyfob Partition 7 keyfob Partition 8 keyfob Zone _____ Assigned to mo...

Page 11: ... keyfob Partition 8 keyfob Table 11 Module programming settings continued Location Segment 1 Segment 2 Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4 Input option 1 5 Input option 2 _ 6 8 Not used Partition 1 keyfob Partition 2 keyfob Partition 3 keyfob Partition 4 keyfob Partition 5 keyfob Partition 6 keyfob Partition 7 keyfob Partition 8 keyfob Zone...

Page 12: ...b Partition 6 keyfob Partition 7 keyfob Partition 8 keyfob Table 11 Module programming settings continued Location Segment 1 Segment 2 Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4 Input option 1 5 Input option 2 _ 6 8 Not used Partition 1 keyfob Partition 2 keyfob Partition 3 keyfob Partition 4 keyfob Partition 5 keyfob Partition 6 keyfob Partition ...

Page 13: ...E P 1 Enable sensor 2 Supervised 3 Fire supervision 4 Input option 1 5 Input option 2 _ 6 8 Not used Partition 1 keyfob Partition 2 keyfob Partition 3 keyfob Partition 4 keyfob Partition 5 keyfob Partition 6 keyfob Partition 7 keyfob Partition 8 keyfob Zone _____ Assigned to module _____ RM HE P 1 Enable sensor 2 Supervised 3 Fire supervision 4 Input option 1 5 Input option 2 _ 6 8 Not used Partit...

Page 14: ...ce could void the user s authority to operate the equip ment Panel Compatibility compatible with all NetworX control panels except CF commercial fire panels Frequency 319 5 MHz Wireless range 600 feet 183 m open air Power Requirements 12 0 VDC provided by panel Current Draw 75 mA maximum Operating Temperature 32 to 120 F 0 to 49 C Storage Temperature 30 to 140 F 34 to 60 C Humidity 90 relative non...

Reviews: