CHAPTER 5: SETTINGS
SYSTEM SETUP
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
5-173
5
IEC 61850–90–5 PMU 1 configuration
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
BASIC CONFIGURATION
PMU 1
PMU 1 BASIC
CONFIGURATION
90-5 PMU 1 CONFIGURATION
PMU1 LDINST
— A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
logical device.
5.5.7.10 PMU calibration
SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PHASOR MEASUREMENT UNIT 1(6)
PMU 1(6)
CALIBRATION
90-5 PMU 1
CONFIGURATION
PMU 1 LDINST:
PMU1
Range: 64 char ASCII text
As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64
characters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.
PMU 1
CALIBRATION
PMU 1 VA CALIBRATION
ANGLE: 0.00
°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 VA CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 VB CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 VB CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 VC CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 VC CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 VX CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 VX CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 IA CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 IA CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 IB CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 IB CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 IC CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 IC CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
PMU 1 IG CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
PMU 1 IG CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%