CHAPTER 1: INTRODUCTION

SPECIFICATIONS

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

1–9

Communications specifications

ETHERNET (COPPER)

Modes:......................................................................10/100 MB (auto-detect)
Connector:..............................................................RJ-45
SNTP clock synchronization error: ..............<200 ms (typical)
Protocol: ..................................................................Modbus TCP

RS485 PORT

Port: ...........................................................................opto-isolated
Baud rates:.............................................................up to 115 kbps
Protocol: ..................................................................Modbus RTU, half-duplex
Maximum distance: ...........................................1200 m
Isolation:..................................................................2 kV

USB PORT

Standard specification:....................................Compliant with both USB 2.0 and USB 1.1
Data transfer rate:..............................................USB device emulating serial communications port at 

115 kbps

Connector:..............................................................USB2.0 Mini-B

Testing and certification

TESTING AND CERTIFICATION

Test

Reference Standard

Test Level

Dielectric Voltage Withstand:

EN60255-5

2.0 KV 

Impulse Voltage Withstand:

EN60255-5

5 KV

Insulation Resistance:

EN60255-5

500 V DC > 100 Mohm

Damped Oscillatory:

IEC61000-4-18/IEC60255-22-1

2.5 KV CM, 1 KV DM

Electrostatic Discharge:

EN61000-4-2/IEC60255-22-2

Level 4

RF Immunity:

EN61000-4-3/IEC60255-22-3

Level 3

Fast Transient Disturbance:

EN61000-4-4/IEC60255-22-4

Level 4

Surge Immunity:

EN61000-4-5/IEC60255-22-5

Level 3 & 4

Conducted RF Immunity:

EN61000-4-6/IEC60255-22-6

Level 3

Power magnetic Immunity:

IEC61000-4-8

Level 4

Voltage Dip & Interruption:

IEC61000-4-11

0,40,70% dips 250/300cycle 

interrupts

Radiated & Conducted Emissions: CISPR11 /CISPR22/ IEC60255-25

Class A

Ingress Protection:

IEC60529

IP20 (base unit) IP54 (Control 

Panel)

Environmental  (Cold):

IEC60068-2-1

-20

o

C 16 hrs 

Environmental  (Dry heat):

IEC60068-2-2

85

o

C 16hrs 

Relative Humidity Cyclic:

IEC60068-2-30

6-day  variant 2

Fast Transient Disturbance:

IEEE C37.90.1

4 KV CM & DM

SWC Damped Oscillatory:

IEEE C37.90.1

2.5 KV CM

Electrostatic Discharge:

IEEE C37.90.3

8 KV CD, 15 KV AD

Summary of Contents for MX350

Page 1: ...N 1601 9071 A2 GE publication code GEK 113497A Copyright 2010 GE Multilin IISO9001 2000 G E M ULTILI N R E GISTERE D 1601 9071 A2 MX350 Automatic Transfer Control System Low voltage power transfer co...

Page 2: ...ad EnerVista MX350 Setup and FlexLogic are registered trademarks of GE Multilin Inc The contents of this manual are the property of GE Multilin Inc This documentation is furnished on license and may n...

Page 3: ...Mechanical installation 2 1 Dimensions 2 1 Product identification 2 2 Mounting 2 2 Module withdrawal and insertion 2 4 Module and terminal identification 2 6 Electrical installation 2 7 Power supply...

Page 4: ...go Transfer Alarm Panel CTAP option 5 7 Common ATS setpoints 5 8 Current and voltage transformers 5 9 Inputs 5 10 Outputs 5 10 Communications setpoints 5 10 System 5 12 Events 5 13 Zenith 5 13 Operati...

Page 5: ...testing Integrated pushbuttons and LED indicators reduce external components and wiring DIN rail and Panel Mounting Multiple communication protocols allows simple integration into monitoring and cont...

Page 6: ...tputs 5 to 32 contact inputs The following option packages are available Option A Full function ATS control with full sensing and control capabilities depending on order option Expanded diagnostics hi...

Page 7: ...up to 256 cycles each 16 samples sec Auto Load Shed with voltage frequency and kW triggers Option C Option Package B plus 4 additional inputs and outputs total 8 in 8 out Option D Option Package C plu...

Page 8: ...CONTROLLER 170VDC RS485 MODBUS RTU ETHERNET MODBUS TCP IP NOTE 1 K CARD P ENGINE START CONTACT I O CARD 24VDC TO K CARD AND I O CARD SUPPLIED BY OTHERS 3 CT S 1 CT NOTE 1 TO SOURCE 2 NOTE 1 FOURTH PO...

Page 9: ...er switch types to be controlled by the Controller are Standard Open Transition Delayed Transition and Closed Transition The figure below shows the one line diagram for all three types Figure 4 Automa...

Page 10: ...steps of 0 1 programmable Dropout 50 0 to 62 9 Hz in steps of 0 1 programmable Time delay No programmable time delay Accuracy 0 05 Hz UNDERFREQUENCY Pickup level 45 0 to 59 9 Hz in steps of 0 1 progr...

Page 11: ...ni B for laptop computer connection Metering and monitoring specifications EVENT RECORDER Capacity 256 events Data storage non volatile memory FREQUENCY METERING Range 40 00 to 70 00 Hz in steps of 0...

Page 12: ...perate time 10 ms Maximum contact load 10 mA at 5 V DC Maximum switching rate 300 operations per minute no load 30 operations per minute load Mechanical life 10 000 000 operations Continuous current 1...

Page 13: ...Insulation Resistance EN60255 5 500 V DC 100 Mohm Damped Oscillatory IEC61000 4 18 IEC60255 22 1 2 5 KV CM 1 KV DM Electrostatic Discharge EN61000 4 2 IEC60255 22 2 Level 4 RF Immunity EN61000 4 3 IEC...

Page 14: ...Council Directive According to CE compliance Low voltage directive EN60255 5 EN60947 1 EN60947 6 1 EMC Directive EN61000 6 2 EN61000 6 4 ISO Manufactured under a registered quality program ISO9001 EN...

Page 15: ...gure 5 MX350 order codes Example of an MX350 order code MX350 GEHE3BBAKLL MX350 with graphical control panel incl USB port English language display high voltage control power supply 84 to 250 VDC or 6...

Page 16: ...1 12 MX350 AUTOMATIC TRANSFER CONTROL SYSTEM INSTRUCTION MANUAL ORDER CODES FOR MX350 CHAPTER 1 INTRODUCTION...

Page 17: ...anical installation This section describes the mechanical installation of the MX350 system including dimensions for mounting and information on module withdrawal and insertion Dimensions The MX350 is...

Page 18: ...e panel of the MX350 This label indicates the product model serial number firmware revision and date of manufacture Figure 2 MX350 label Mounting The MX350 can be mounted three ways standard panel mou...

Page 19: ...ation and or within an appropriate enclosure Figure 4 DIN rail mounting The screw mount for high vibration environments is illustrated below 4 40x3 8in SELF TAP PAN HD PHILIPS QTY 6 SUPPLIED GE PART N...

Page 20: ...ular protection system This allows for easy withdrawal and insertion of modules for fast replacement Modules must only be replaced in their original factory configured slots Use the following procedur...

Reviews: