CHAPTER 4: PROGRAMMING
S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–27
Table 4–3: Analog Output Parameters
PARAMETER
RANGE
STEP
PARAMETER
RANGE
STEP
Phase A Current
0 to 150%
1%
Phase B kVA
0 to 65400
1 kVA
Phase B Current
0 to 150%
1%
Phase C PF
0.01 lead to 0.01
lag
0.01
Phase C Current
0 to 150%
1%
Phase C kW
–32500 to
+32500
1 kW
Neutral Current
0 to 150%
1%
Phase C kvar
–32500 to
+32500
1 kvar
Average Phase
Current
0 to 150%
1%
Phase C kVA
0 to 65400
1 kVA
Current Unbalance
0 to 100.0%
0.1%
3 Phase +kWh Used
0 to 65400
1 kWh
Voltage Van
0 to 200%
1%
3 Phase +kvarh Used
0 to 65400
1 kvarh
Voltage Vbn
0 to 200%
1%
3 Phase –kWh Used
0 to 65400
1 kWh
Voltage Vcn
0 to 200%
1%
3 Phase –kvarh Used
0 to 65400
1 kvarh
Voltage Vab
0 to 200%
1%
3 Phase kVAh Used
0 to 65400
1 kVAh
Voltage Vbc
0 to 200%
1%
Ph. A Current
Demand
0 to 7500
1 A
Voltage Vca
0 to 200%
1%
Ph. B Current
Demand
0 to 7500
1 A
Average Phase
Voltage
0 to 200%
1%
Ph. C Current
Demand
0 to 7500
1 A
Average Line Voltage
0 to 200%
1%
Neutral Current
Demand
0 to 7500
1 A
Voltage Unbalance
0 to 100.0%
0.1%
3 Phase kW Demand
–32500 to
+32500
1 kW
Frequency
00.00 to 75.00 Hz
0.01 Hz
3 Phase kvar Demand
–32500 to
+32500
1 kvar
3 Phase PF
0.01 lead to 0.01
lag
0.01
3 Phase kVA Demand
0 to 65400
1 kVA
3 Phase kW
–32500 to
+32500
1 kW
3 Phase Current THD
0.0 to 100%
0.1%
3 Phase kvar
–32500 to
+32500
1 kvar
3 Phase Voltage THD
0.0 to 100%
0.1%
3 Phase kVA
0 to 65400
1 kVA
Phase A Current THD
0.0 to 100%
0.1%
3 Phase MW
–3250.0 to
+3250.0
0.1 MW
Phase B Current THD
0.0 to 100%
0.1%
3 Phase Mvar
–3250.0 to
+3250.0
0.1 Mvar
Phase C Current THD
0.0 to 100%
0.1%