5-4
MIGII Digital Protection for Electrical Machines
GEK-113188A
5.2 MAIN SETTINGS
5 SETTINGS
5
5.2.2 NEGATIVE SEQUENCE IOC 46
NEG SEQ IOC 46
Curve 46
NEG SEQ IOC 46
TD Mult 46
Range: Mod. Inverse – Definite Time
Default: TDE
Range: 1 - 100
Default: 1
Step: 1
NEG SEQ IOC 46
Trip enable 46
ENTER
MENU
MAIN SETTINGS
NEG SEQ IOC 46
ENTER
MAIN SETTINGS
NEG SEQ IOC 46
NEG SEQ IOC 46
Enable 46
Range: Yes/No
Default: No
Range: Yes/No
Default: Yes
NEG SEQ IOC 46
Pickup 46
Range: 0.05 - 0.99 FLC
Default: 0.1 FLC
NEG SEQ IOC 46
Delay 46
Range: 0 – 600 s
Default: 0 s
Step: 0.1
Summary of Contents for Multilin MIGII
Page 2: ......