GEK-113000T
F650 Digital Bay Controller
5-5
5 BOOTCODE AND FIRMWARE UPGRADE
5.2 BOOT CODE UPGRADE
5
5.2BOOT CODE UPGRADE
Boot code upgrade is performed using EnerVista 650 Setup. It is required that there is no active communication between
the program and the relay, and that no configuration file is open.
In this case, menu option
Upgrade Boot code
will be enabled under the EnerVista 650 Setup
Communication
menu.
During the boot code upgrading process, all the data stored in the relay will be lost, so it is required to save all calibration,
settings, oscillography, etc. from the relay before the upgrade. It is extremely important to save the relay settings and
calibration before continuing with the process.
Figure 5–5: LOST DATA WARNING MESSAGE
To upgrade the boot code, it is required to connect an RS232 cable to the front of the relay, and an Ethernet cable to the
rear port (COM3).
The serial communication parameters will be the ones selected in the
Communications > Computer
menu, where the
COMX port (the port to be used in the upgrade) must be selected.
If the connection is made directly from the PC to the relay it is necessary to use a 10/100 Base T crossover cable. During
the upgrade, the system will show the following message indicating the procedure to be followed.
Figure 5–6: SERIAL AND ETHERNET CONNECTIONS FOR BOOT CODE UPGRADE
Summary of Contents for Multilin GEK-113000T
Page 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Page 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Page 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Page 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Page 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...