APPENDIX B
B.4 MEMORY MAPPING
B
A58B
...Repeated for Volts Per Hertz 2
Volts Per Hertz Actual Values (Read Only) (2 modules)
A5A0
Volts Per Hertz 1
0 to 65.535
pu
0.001
F001
0
A5A1
Volts Per Hertz 2
0 to 65.535
pu
0.001
F001
0
FlexCurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
0 to 1
---
1
F102
0 (Disabled)
A701
Non-Volatile Latch 1 Type
0 to 1
---
1
F519
0 (Reset
Dominant)
A702
Non-Volatile Latch 1 Set
0 to 4294967295
---
1
F300
0
A704
Non-Volatile Latch 1 Reset
0 to 4294967295
---
1
F300
0
A706
Non-Volatile Latch 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A707
Non-Volatile Latch 1 Events
0 to 1
---
1
F102
0 (Disabled)
A708
Reserved (4 items)
---
---
---
F001
0
A70C
...Repeated for Non-Volatile Latch 2
A718
...Repeated for Non-Volatile Latch 3
A724
...Repeated for Non-Volatile Latch 4
A730
...Repeated for Non-Volatile Latch 5
A73C
...Repeated for Non-Volatile Latch 6
A748
...Repeated for Non-Volatile Latch 7
A754
...Repeated for Non-Volatile Latch 8
A760
...Repeated for Non-Volatile Latch 9
A76C
...Repeated for Non-Volatile Latch 10
A778
...Repeated for Non-Volatile Latch 11
A784
...Repeated for Non-Volatile Latch 12
A790
...Repeated for Non-Volatile Latch 13
A79C
...Repeated for Non-Volatile Latch 14
A7A8
...Repeated for Non-Volatile Latch 15
A7B4
...Repeated for Non-Volatile Latch 16
Frequency Rate of Change (Read/Write Setting) (4 modules)
A900
Frequency Rate of Change 1 Function
0 to 1
---
1
F102
0 (Disabled)
A901
Frequency Rate of Change 1 OC Supervision
0 to 30
pu
0.001
F001
200
A902
Frequency Rate of Change 1 Min
20 to 80
Hz
0.01
F001
4500
A903
Frequency Rate of Change 1 Max
20 to 80
Hz
0.01
F001
6500
A904
Frequency Rate of Change 1 Pickup Delay
0 to 65.535
s
0.001
F001
0
A905
Frequency Rate of Change 1 Reset Delay
0 to 65.535
s
0.001
F001
0
A906
Frequency Rate of Change 1 Block
0 to 4294967295
---
1
F300
0
A908
Frequency Rate of Change 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A909
Frequency Rate of Change 1 Events
0 to 1
---
1
F102
0 (Disabled)
A90A
Frequency Rate of Change 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A90B
Frequency Rate of Change 1 Trend
0 to 2
---
1
F224
0 (Increasing)
A90C
Frequency Rate of Change 1 Pickup
0.1 to 15
Hz/s
0.01
F001
50
A90D
Frequency Rate of Change 1 OV Supervision
0.1 to 3
pu
0.001
F001
700
A90E
Frequency Rate of Change 1 Reserved (3 items)
0 to 1
---
1
F001
0
A911
...Repeated for Frequency Rate of Change 2
A922
...Repeated for Frequency Rate of Change 3
A933
...Repeated for Frequency Rate of Change 4
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960
Restricted Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
A961
Restricted Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A962
Restricted Ground Fault 1 Pickup
0.005 to 30
pu
0.001
F001
80
A963
Restricted Ground Fault 1 Slope
0 to 100
%
1
F001
40
Table B–10: MODBUS MEMORY MAP (Sheet 47 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...