GE Multilin
G60 Generator Protection System
2-23
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
REMOTE RTD INPUTS
Wire type:
three-wire
Sensor type:
100
Ω
platinum (DIN 43760), 100
Ω
nickel, 120
Ω
nickel, 10
Ω
copper
RTD sensing current:
3 mA
Range:
–40 to 200°C
Accuracy: ±2°C
Lead resistance:
25
Ω
maximum for Pt and Ni type; 3
Ω
max. for Cu type
Isolation:
36 Vpk
IRIG-B INPUT
Amplitude modulation:
1 to 10 V pk-pk
DC shift:
TTL–Compatible
Input impedance:
50 k
Ω
Isolation:
2 kV
REMOTE INPUTS (IEC 61850 GSSE/GOOSE)
Input points:
32, configured from 64 incoming bit pairs
Remote devices:
16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Remote DPS inputs:
5
DIRECT INPUTS
Input points:
32
Remote devices:
16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
Yes, No
Data rate:
64 or 128 kbps
CRC:
32-bit
CRC alarm:
Responding to:
Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
1 to 1000 in steps of 1
Unreturned message alarm:
Responding to:
Rate of unreturned messages in the ring
configuration
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
1 to 1000 in steps of 1
TELEPROTECTION
Input points:
16
Remote devices:
3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
No
Data rate:
64 or 128 kbps
CRC:
32-bit
2.2.6 POWER SUPPLY
LOW RANGE
Nominal DC voltage:
24 to 48 V
Minimum DC voltage:
20 V
Maximum DC voltage:
60 V
Voltage loss hold-up:
20 ms duration at nominal
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
125 to 250 V
Minimum DC voltage:
88 V
Maximum DC voltage:
300 V
Nominal AC voltage:
100 to 240 V at 50/60 Hz
Minimum AC voltage:
88 V at 25 to 100 Hz
Maximum AC voltage:
265 V at 25 to 100 Hz
Voltage loss hold-up:
200 ms duration at nominal
ALL RANGES
Volt withstand:
2
×
Highest Nominal Voltage for 10 ms
Power consumption:
typical = 15 to 20 W/VA
maximum = 50 W/VA
contact factory for exact order code con-
sumption
INTERNAL FUSE
RATINGS
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
INTERRUPTING CAPACITY
AC:
100 000 A RMS symmetrical
DC:
10 000 A
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...