8-4
G60 Generator Protection System
GE Multilin
8.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS
8 THEORY OF OPERATION
8
Equations from the “Current Transformation” and “Voltage Transformation” columns are used to derive inputs to the three
(AB, BC, and CA) phase distance elements. For example, if the CTs are located at the delta side of the Delta-Wye 11 trans-
former, and a given zone is set to look through the transformer into the system connected to the Wye winding, the CT loca-
tion setting for that zone shall be set to Dy11 and the relay would use
instead of a traditional
for the AB
phase distance element.
The current supervision pickup setting applies to the currents specified in the “Current Transformation” columns.
A distance zone originates at the location of the VTs (regardless of the location of the CTs). For more information on set-
tings please refer to Chapter 9: Application of Settings.
8.1.2 EXAMPLE
Consider the system shown below:
Figure 8–2: SAMPLE SYSTEM CONFIGURATION
Normally, in order to respond to the fault shown in the figure, a distance relay shall be applied at the relaying point X. The
relay input signals at this location are shown in the following table.
If installed at the location X, the relay would use the following input signals for its phase AB distance element:
V
=
V
AB
= 77.402 kV
∠
57.5° primary or 29.49 V
∠
57.5° secondary
I
=
I
A
–
I
B
= 2.576 kA
∠
–27.6° primary or 42.93 A
∠
–27.6° secondary
And consequently it would see an apparent impedance of:
Z
app
=
V
/
I
= 30.05
Ω
∠
85° primary or 0.687
Ω
∠
85° secondary
INPUT
PRIMARY
SECONDARY
VA
100.4 kV
∠
–7.32°
38.25 V
∠
–7.32°
VB
97.23 kV
∠
–53.4°
37.04 V
∠
–53.4°
VC
181.8 kV
∠
–150.0°
69.26 V
∠
–150.0°
IA
1.288 kA
∠
–27.6°
21.47 A
∠
–27.6°
IB
1.288 kA
∠
152.4°
21.47 A
∠
152.4°
IC
0
0
3
I
B
–
I
A
I
B
–
837727A2.CDR
AB
wye, 330 lag
°
0.688
85°
Ω∠
2.57
Ω∠
88.4°
150 MVA, 10%
13.8kV/315kV
Z = 30.11
85°
L
Ω∠
VT = 315kV/120V
CT = 300:5
VT = 13.8kV/120V
CT = 8000:5
delta
H
X
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...