GE Multilin
G60 Generator Protection System
6-19
6 ACTUAL VALUES
6.3 METERING
6
f) POWER METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
POWER
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text is replaced by whatever name was programmed by the user for the associated source (see
SETTINGS
SYSTEM
SETUP
SIGNAL SOURCES
).
When VTs are configured in wye, the G60 calculates power in each phase and three-phase power is measured as
S = V
A
x Î
A
+ V
B
x Î
B
+ V
C
x Î
C
(EQ 6.1)
When VTs are configured in delta, the G60 does not calculate power in each phase and three-phase power is measured as
S = V
AB
x Î
A
+ V
CB
x Î
C
(EQ 6.2)
where
S is the apparent power
V
A
, V
B
, V
C
, I
A
, I
B
, I
C
are phase voltage and phase current phasors
POWER
SRC 1
SRC 1 REAL POWER
3
φ
: 0.000 W
MESSAGE
SRC 1 REAL POWER
φ
a: 0.000 W
MESSAGE
SRC 1 REAL POWER
φ
b: 0.000 W
MESSAGE
SRC 1 REAL POWER
φ
c: 0.000 W
MESSAGE
SRC 1 REACTIVE PWR
3
φ
: 0.000 var
MESSAGE
SRC 1 REACTIVE PWR
φ
a: 0.000 var
MESSAGE
SRC 1 REACTIVE PWR
φ
b: 0.000 var
MESSAGE
SRC 1 REACTIVE PWR
φ
c: 0.000 var
MESSAGE
SRC 1 APPARENT PWR
3
φ
: 0.000 VA
MESSAGE
SRC 1 APPARENT PWR
φ
a: 0.000 VA
MESSAGE
SRC 1 APPARENT PWR
φ
b: 0.000 VA
MESSAGE
SRC 1 APPARENT PWR
φ
c: 0.000 VA
MESSAGE
SRC 1 POWER FACTOR
3
φ
: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
a: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
b: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
c: 1.000
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...