GE Multilin
G60 Generator Protection System
5-143
5 SETTINGS
5.5 FLEXLOGIC
5
ELEMENT:
Selector switch
SELECTOR 1 POS Y
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
SELECTOR 2
Same set of operands as shown above for SELECTOR 1
ELEMENT:
Setting group
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
ELEMENT:
Sub-harmonic stator
ground fault detector
SH STAT GND STG1 PKP
SH STAT GND STG1 DPO
SH STAT GND STG1 OP
SH STAT GND STG2 PKP
SH STAT GND STG2 DPO
SH STAT GND STG2 OP
SH STAT GND OC PKP
SH STAT GND OC DPO
SH STAT GND OC OP
SH STAT GND TRB OP
Stage 1 of the sub-harmonic stator ground protection has picked up
Stage 1 of the sub-harmonic stator ground protection has dropped out
Stage 1 of the sub-harmonic stator ground protection has operated
Stage 2 of the sub-harmonic stator ground protection has picked up
Stage 2 of the sub-harmonic stator ground protection has dropped out
Stage 2 of the sub-harmonic stator ground protection has operated
Ground over current element of the sub-harmonic stator ground protection
has picked up
Ground over current element of the sub-harmonic stator ground protection
has dropped out
Ground over current element of the sub-harmonic stator ground protection
has operated
Sub-harmonic stator ground module trouble has operated
ELEMENT:
Split phase
protection
SPLIT PHASE A PKP
SPLIT PHASE A DPO
SPLIT PHASE A OP
SPLIT PHASE B PKP
SPLIT PHASE B DPO
SPLIT PHASE B OP
SPLIT PHASE C PKP
SPLIT PHASE C DPO
SPLIT PHASE C OP
SPLIT PHASE OP
SPLIT PHASE PKP
SPLIT PHASE DPO
Phase A of the split phase protection has picked up
Phase A of the split phase protection has dropped out
Phase A of the split phase protection has operated
Phase B of the split phase protection has picked up
Phase B of the split phase protection has dropped out
Phase B of the split phase protection has operated
Phase C of the split phase protection has picked up
Phase C of the split phase protection has dropped out
Phase C of the split phase protection has operated
The split phase protection has operated
The split phase protection has picked up
The split phase protection has dropped out
ELEMENT:
Disturbance
detector
SRC1 50DD OP
SRC2 50DD OP
SRC3 50DD OP
SRC4 50DD OP
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
ELEMENT:
VTFF (Voltage
transformer fuse
failure)
SRC1 VT FF OP
SRC1 VT FF DPO
SRC1 VT FF VOL LOSS
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 10% and V1 below 5%
of nominal)
SRC1 VT NEU WIRE OPEN
Source 1 VT neutral wire open detected.When the VT is connected in Delta,
this function should not be enabled because there is no neutral wire for Delta
connected VT.
SRC2 VT FUSE FAIL to SRC4
Same set of operands as shown for SRC1 VT FUSE FAIL
ELEMENT:
Stator differential
STATOR DIFF OP
STATOR DIFF PKP A
STATOR DIFF PKP B
STATOR DIFF PKP C
STATOR DIFF OP A
STATOR DIFF OP B
STATOR DIFF OP C
STATOR DIFF DPO A
STATOR DIFF DPO B
STATOR DIFF DPO C
STATOR DIFF SAT A
STATOR DIFF SAT B
STATOR DIFF SAT C
STATOR DIFF DIR A
STATOR DIFF DIR B
STATOR DIFF DIR C
At least one phase of stator differential has operated
Phase A of stator differential has picked up
Phase B of stator differential has picked up
Phase C of stator differential has picked up
Phase A of stator differential has operated
Phase B of stator differential has operated
Phase C of stator differential has operated
Phase A of stator differential has dropped out
Phase B of stator differential has dropped out
Phase C of stator differential has dropped out
Phase A of stator differential has is saturated
Phase B of stator differential has is saturated
Phase C of stator differential has is saturated
Phase A of stator differential phase comparison has been satisfied
Phase B of stator differential phase comparison has been satisfied
Phase C of stator differential phase comparison has been satisfied
Table 5–15: G60 FLEXLOGIC OPERANDS (Sheet 6 of 9)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for Multilin g60
Page 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Page 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...