GE Multilin
G60 Generator Protection System
5-91
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.18 INSTALLATION
PATH: SETTINGS
PRODUCT SETUP
INSTALLATION
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until
RELAY SETTINGS
is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
UNIT NOT PROGRAMMED
self-test error message is displayed until the relay is put into the "Programmed" state.
The
RELAY NAME
setting allows the user to uniquely identify a relay. This name will appear on generated reports.
INSTALLATION
RELAY SETTINGS:
Not Programmed
Range: Not Programmed, Programmed
MESSAGE
RELAY NAME:
Relay-1
Range: up to 20 alphanumeric characters
Summary of Contents for Multilin g60