A2 Metering
745
Transformer Management Relay
Actual
V
alues
http://www.GEindustrial.com/multilin
6–6
GE Multilin
The fundamental frequency current magnitudes for Winding 1 phases A, B, and C,
neutral, and ground are shown. The current angle for Phase A is always set to 0° as
it is used as reference for all other currents, both measured and derived. The
maximum specified load and average phase current are also shown for the specified
winding.
c) Positive Sequence Current
PATH: ACTUAL VALUES
!"
A2 METERING
!
CURRENT
!"
POSITIVE SEQUENCE
All positive-, negative-, and zero- sequence component phase angles are
referenced to the Winding 1 Phase A current
The positive-sequence current magnitudes and phase values for Windings 1, 2, and
3 are shown here.
d) Negative Sequence Current
PATH: ACTUAL VALUES
!"
A2 METERING
!
CURRENT
!"
NEGATIVE SEQUENCE
The negative-sequence current magnitudes and phase values for Windings 1, 2, and
3 are shown here.
e) Zero Sequence Current
PATH: ACTUAL VALUES
!"
A2 METERING
!
CURRENT
!"
ZERO SEQUENCE
The zero-sequence current magnitudes and phase values for Windings 1, 2, and 3
are shown here.
!
POSITIVE
[
!
]
SEQUENCE
W1 POS SEQ CURRENT:
0 A at
0° Lag
MESSAGE
W2 POS SEQ CURRENT:
0 A at
0° Lag
MESSAGE
W3 POS SEQ CURRENT:
0 A at
0° Lag
!
NEGATIVE
[
!
]
SEQUENCE
W1 NEG SEQ CURRENT:
0 A at
0° Lag
MESSAGE
W2 NEG SEQ CURRENT:
0 A at
0° Lag
MESSAGE
W3 NEG SEQ CURRENT:
0 A at
0° Lag
!
ZERO SEQUENCE
[
!
]
W1 ZERO SEQ CURRENT:
0 A at
0° Lag
MESSAGE
W2 ZERO SEQ CURRENT:
0 A at
0° Lag
MESSAGE
W3 ZERO SEQ CURRENT:
0 A at
0° Lag
NOTE