6–44
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S1 RELAY SETUP
CHAPTER 6: SETPOINTS
IEC 61850 GOOSE
communications
The 350 firmware supports IEC61850 GOOSE communications on the optional
communications daughter board.
Portions of the IEC61850 standard not pertaining to GOOSE, are not implemented in the
350 relay.
The 350 relay does not support
•
an IEC61850 MMS server
•
the mapping of analogue values to data points in data sets in either the transmit or
receive direction
•
a file system to maintain SCL, ICD or CID files, for IEC61850 GOOSE. As such the
implementation stores GOOSE configuration using MODBUS set points.
Configuration of transmission and reception settings for the GOOSE feature are performed
using EnerVista SR3 Setup Software.
The 350 firmware accepts GOOSE messages from UR, F650 and UR Plus. The
interoperability with other manufacturers will be guaranteed in almost all cases, by
implementing the reception side with nested structures (one level of nesting) and all the
standard data types.
0xEF02
CLPNtrlIOC1 BLK
0xEF42
CLPNtrlIOC2 BLK
0xEF82
CLP GndIOC1 BLK
0xEFC2
CLP GndIOC2 BLK
0xF002
Ph IOC1 Block
0xF042
Ntrl IOC1 Block
0xF082
Gnd IOC1 Block
0xF0C2
Ph TOC1 Block
0xF102
Ntrl TOC1 Block
0xF142
Gnd TOC1 Block
0xF182
Ph IOC2 Block
0xF1C2
Ntrl IOC2 Block
0xF202
Gnd IOC2 Block
0xF302
SGnd TOC1 Block
0xF342
Ntrl Dir Block
0xF382
Gnd Dir Block
0xF3C2
NegSeq OV Block
0xF402
Ntrl OV Block
0xF442
Ph OV1 Block
0xF482
Ph UV1 Block
0xF4C2
Aux OV Block
0xF502
Aux UV Block
0xF542
UndrFreq1 Block
0xF582
UndrFreq2 Block
0xF5C2
OverFreq1 Block
0xF602
OverFreq2 Block
0xF642
SGnd IOC1 Block
0xF682
SGnd IOC2 Block
0xF6C2
NSeq IOC Block
Code
Type
Definition