CHAPTER 7: TESTING
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
7–5
A2 METERING DATA
CURRENT METERING
:
7.2.4
GE Digital Energy 50:0.025 Ground Accuracy Test
The 469 specification for GE Grid Solutions 50:0.025 ground current input accuracy is
±
0.5% of CT rated primary (25 A). Perform the steps below to verify accuracy.
Alter the following settings:
S2 SYSTEM SETUP
CURRENT SENSING
GROUND CT:
“50:0.025”
Measured values should be
±
0.125 A.
Inject the values shown in the table below either as primary values
into a GE Grid Solutions 50:0.025 Core Balance CT or as secondary
values that simulate the core balance CT.
Verify accuracy of the measured values.
View the measured values in:
A2 METERING DATA
CURRENT METERING
7.2.5
RTD Accuracy Test
The 469 specification for RTD input accuracy is
±
2
°
. Perform the steps below.
Alter the following settings:
S8 RTD TEMPERATURE
RTD TYPES
STATOR RTD TYPE:
“100 Ohm Platinum” (select
desired type)
S8 RTD TEMPERATURE
RTD #1
RTD #1 APPLICATION:
“Stator” (repeat for RTDs 2 to
12)
Measured values should be
±
2
°
C or ±4°F.
Alter the resistances applied to the RTD inputs as per the table below
to simulate RTDs.
Verify accuracy of the measured values.
View measured values in:
INJECTED
CURRENT
1 A UNIT
EXPECTED
CURRENT
READING
MEASURED
GROUND
CURRENT
MEASURED DIFFERENTIAL
CURRENT
PHASE A
PHASE B
PHASE C
0.1 A
100 A
0.2 A
200 A
0.5 A
500 A
1.0 A
1000 A
PRIMARY
INJECTED
CURRENT
SECONDARY
INJECTED
CURRENT
EXPECTED
CURRENT
READING
MEASURED
GROUND
CURRENT
0.25 A
0.125 mA
0.25 A
1 A
0.5 mA
1.00 A
10 A
5 mA
10.00 A
25 A
12.5 mA
25.00 A
Summary of Contents for Masoneilan 469 Series
Page 4: ......
Page 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Page 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Page 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...