APPENDIX B
SCREEN DESCRIPTION FOR BASIC SETUP MENU – 2/2
ZERO
When displayed, empty the tank (or simulate) so that displacer is fully out of liquid. Wait
until the displacer is stable then press * to define the low reference (REF L).
SPAN
When displayed, fill the tank (or simulate) so that displacer is fully immersed in liquid. Wait
until the displacer is stable then press * to define the high reference (REF H).
SAVE
Validate by pressing the * to start the saving procedure of parameters previously entered
in the instrument memory.
CANCEL
Validate by pressing the * to cancel the parameters saving procedure.
CHANGE S
PECIFIC
G
RAVITY
Enter that function to set the Specific Gravity of Service in case it is different from the
Specific Gravity of Calibration.
S
PECIFIC
G
RAVITY
of
SERV
ICE
Validate by pressing the * to set the Specific Gravity of the liquid of service if it is different
from the Specific Gravity of Calibration. Settable value ranges from 0.001 to 10.
L
OW
S
PECIFIC
G
RAVITY of
SERV
ICE
Used in case of an interface instrument. Validate by pressing the * to set the Specific
Gravity of the lighter liquid used in service if it is different from LSG CAL. Settable values
range from 0.001 to the value of HSG SER.
H
IGH
S
PECIFIC
G
RAVITY of
SERV
ICE
Used in case of an interface instrument. Validate by pressing the * to set the Specific
Gravity of the heavier liquid in service if it is different from HSG CAL. Settable values range
from LSG SER to 10.0.
SAVE
Validate by pressing the * to start the saving procedure of configuration parameters
previously entered in the instrument memory.
CANCEL
Validate by pressing the * to cancel the parameters saving procedure.
↑
BACK
Return to previous menu.