GE Multilin
M60 Motor Protection System
B-39
APPENDIX B
B.4 MEMORY MAPPING
B
66B0
Underpower 1 Trip Reset Delay
0 to 600
s
0.01
F001
100
66B1
Underpower 1 Block
0 to 4294967295
---
---
F300
0
66B3
Underpower 1 Target
0 to 2
---
1
F109
0 (Self-reset)
66B4
Underpower 1 Events
0 to 1
---
1
F102
0 (Disabled)
66B5
...Repeated for Underpower 2
Reduced Voltage Starting (Read/Write Grouped Setting)
6750
Reduced Voltage Start Function
0 to 1
---
1
F102
0 (Disabled)
6751
Reduced Voltage Start Transition Mode
0 to 2
---
1
F095
0 (Current Only)
6752
Reduced Voltage Start FLA
25 to 300
%
1
F001
125
6753
Reduced Voltage Start Timer
1.0 to 600.0
s
0.1
F001
100
6754
Reduced Voltage Start Block
0 to 4294967295
---
1
F300
0
6755
Reduced Voltage Start Target
0 to 2
---
1
F109
0 (Self-Reset)
6757
Reduced Voltage Start Event
0 to 1
---
1
F102
0 (Disabled)
6758
Reserved (5 items)
---
---
1
F001
0
Motor Acceleration Actuals (Read Only Non-Volatile) (5 Modules)
68D0
Motor Acceleration 1 Time/Date
0 to 4294967295
---
1
F050
0
68D2
Motor Acceleration 1 Starting Time
0 to 655.35
s
0.01
F001
0
68D3
Motor Acceleration 1 Effective Current
0 to 999999.999
A
0.001
F060
0
68D5
Motor Acceleration 1 Peak Current
0 to 999999.999
A
0.001
F060
0
68D7
Motor Acceleration 1 Reserved (9 items)
---
---
---
F001
0
68DF
...Repeated for Motor Acceleration 2
68EE
...Repeated for Motor Acceleration 3
68FD
...Repeated for Motor Acceleration 4
690C
...Repeated for Motor Acceleration 5
Motor Acceleration Commands (Read/Write Command)
691F
Motor Acceleration Clear Data Command
0 to 1
---
1
F126
0 (No)
Motor Maximum Starting Rate (Read/Write Setting)
6920
Starts Per Hour Function
0 to 1
---
1
F102
0 (Disabled)
6921
Starts Per Hour Time Interval
1 to 300
min
1
F001
60
6922
Starts Per Hour Maximum Number Of Starts
1 to 16
---
1
F001
3
6923
Starts Per Hour Block
0 to 4294967295
---
1
F300
0
6925
Starts Per Hour Target
0 to 2
---
1
F109
0 (Self-reset)
6926
Starts Per Hour Events
0 to 1
---
1
F102
0 (Disabled)
6927
Reserved (9 items)
---
---
---
F001
0
Motor Time Between Starts (Read/Write Setting)
6930
Time Between Starts Function
0 to 1
---
1
F102
0 (Disabled)
6931
Time Between Starts Minimum Time
0 to 300
min
1
F001
20
6932
Time Between Starts Block
0 to 4294967295
---
1
F300
0
6934
Time Between Starts Target
0 to 2
---
1
F109
0 (Self-reset)
6935
Time Between Starts Events
0 to 1
---
1
F102
0 (Disabled)
6936
Reserved (10 items)
0 to 1
---
1
F001
0
Motor Restart Delay (Read/Write Setting)
6940
Restart Delay Function
0 to 1
---
1
F102
0 (Disabled)
6941
Restart Delay Minimum Time
0 to 50000
s
1
F001
0
6942
Restart Delay Block
0 to 4294967295
---
1
F300
0
6944
Restart Delay Target
0 to 2
---
1
F109
0 (Self-reset)
6945
Restart Delay Events
0 to 1
---
1
F102
0 (Disabled)
6946
Reserved (10 items)
---
---
---
F001
0
Motor Mechanical Jam (Read/Write Grouped Setting)
6950
Mechanical Jam Function
0 to 1
---
1
F102
0 (Disabled)
6951
Mechanical Jam Pickup
1 to 10
x FLA
0.01
F001
200
6952
Mechanical Jam Pickup Delay
0.1 to 600
s
0.01
F001
10
6953
Mechanical Jam Reset Delay
0 to 600
s
0.01
F001
0
6954
Mechanical Jam Block
0 to 4294967295
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 662: ...x M60 Motor Protection System GE Multilin INDEX ...