5-122
M60 Motor Protection System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
ELEMENT:
Motor mechanical
jam
MECHANICAL JAM PKP
MECHANICAL JAM DPO
MECHANICAL JAM OP
The mechanical jam element has picked up
The mechanical jam element has dropped out
The mechanical jam element has operated
ELEMENT:
Motor acceleration
time
MOTOR ACCEL TIME OP
MOTOR ACCEL TIME DPO
The motor acceleration time element has operated
The motor acceleration time element has dropped out
ELEMENT:
Two-speed motor
MOTOR SPD2 TR 2-1 OP
MOTOR SPD2 ACL t OP
MOTOR SPD2 ACL t DPO
Asserted when the motor switches from speed 2 to speed 1
Asserted when the acceleration time function at speed 2 operates.
Asserted when the acceleration time function at speed 2 drops off.
ELEMENT:
Motor thermal model
MOTOR THERMAL PKP
MOTOR THERMAL OP
MOTOR THERMAL DPO
MOTOR RESTART
MOTOR START INHIBIT
MOTOR OFFLINE
MOTOR STARTING
MOTOR RUNNING
MOTOR OVERLOAD
The thermal model element has picked up
The thermal model element has operated
The thermal model element has dropped out
The motor has restarted
A motor start inhibit condition has occurred
The motor is offline
The motor is starting
The motor is running
A motor overload condition has occurred
ELEMENT:
Negative-sequence
overvoltage
NEG SEQ OV1 PKP
NEG SEQ OV1 DPO
NEG SEQ OV1 OP
Negative-sequence overvoltage element has picked up
Negative-sequence overvoltage element has dropped out
Negative-sequence overvoltage element has operated
NEG SEQ OV2...
Same set of operands as shown for NEG SEQ OV1
ELEMENT:
Neutral
instantaneous
overcurrent
NEUTRAL IOC1 PKP
NEUTRAL IOC1 OP
NEUTRAL IOC1 DPO
Neutral instantaneous overcurrent 1 has picked up
Neutral instantaneous overcurrent 1 has operated
Neutral instantaneous overcurrent 1 has dropped out
NEUTRAL IOC2
Same set of operands as shown for NEUTRAL IOC1
ELEMENT:
Neutral overvoltage
NEUTRAL OV1 PKP
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
Neutral overvoltage element 1 has picked up
Neutral overvoltage element 1 has dropped out
Neutral overvoltage element 1 has operated
ELEMENT:
Neutral directional
overcurrent
NTRL DIR OC1 FWD
NTRL DIR OC1 REV
Neutral directional overcurrent 1 forward has operated
Neutral directional overcurrent 1 reverse has operated
NTRL DIR OC2
Same set of operands as shown for NTRL DIR OC1
ELEMENT:
Overfrequency
OVERFREQ 1 PKP
OVERFREQ 1 OP
OVERFREQ 1 DPO
Overfrequency 1 has picked up
Overfrequency 1 has operated
Overfrequency 1 has dropped out
OVERFREQ 2 to 4
Same set of operands as shown for OVERFREQ 1
ELEMENT:
Phase directional
overcurrent
PH DIR1 BLK A
PH DIR1 BLK B
PH DIR1 BLK C
PH DIR1 BLK
Phase A directional 1 block
Phase B directional 1 block
Phase C directional 1 block
Phase directional 1 block
PH DIR2
Same set of operands as shown for PH DIR1
ELEMENT:
Phase
instantaneous
overcurrent
PHASE IOC1 PKP
PHASE IOC1 OP
PHASE IOC1 DPO
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
At least one phase of phase instantaneous overcurrent 1 has picked up
At least one phase of phase instantaneous overcurrent 1 has operated
All phases of phase instantaneous overcurrent 1 have dropped out
Phase A of phase instantaneous overcurrent 1 has picked up
Phase B of phase instantaneous overcurrent 1 has picked up
Phase C of phase instantaneous overcurrent 1 has picked up
Phase A of phase instantaneous overcurrent 1 has operated
Phase B of phase instantaneous overcurrent 1 has operated
Phase C of phase instantaneous overcurrent 1 has operated
Phase A of phase instantaneous overcurrent 1 has dropped out
Phase B of phase instantaneous overcurrent 1 has dropped out
Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 and higher
Same set of operands as shown for PHASE IOC1
Table 5–14: M60 FLEXLOGIC OPERANDS (Sheet 3 of 8)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for M60 UR Series
Page 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Page 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Page 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Page 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...