![GE M-PACT Operating And Installation Instructions Download Page 29](http://html.mh-extra.com/html/ge/m-pact/m-pact_operating-and-installation-instructions_122835029.webp)
28
-
At this stage,
select
the appropriate setting (Note, the presently stored setting has an equals sign before it. Upon selection, this
changes as illustrated):
Press
and the M-PRO will display
-
And
then,
modify
the settings in order to save it in the M-PRO as follows (Note, after modifying the setting, an equals precedes the
stored value):
Press and hold
Press
and the M-PRO will display
S/C Curve
= C03, 69ms @ 6Iset
Fixed S/C Crnt
= 8xI_SET 3200A
Fixed S/C Time
= 1.0s
Fixed S/C Time
→
1.0s
Select
Down
Fixed S/C Time
→
0.9s
Down
Fixed S/C Time
→
0.8s
Select
Down
Fixed S/C Time
= 0.8s