1–10
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 1: INTRODUCTION
1.5.5
CT Dimensions
Thermal overload CT
Ground fault CT
1.5.6
Outputs
RELAY OUTPUTS
Relay pilot duty:...............................................5 A at 120 V AC
5 A at 28 V DC
1.5.7
Communications
DEVICENET
Functionality:....................................................group 2 slave only
Device type:.......................................................motor starter
Order Code
Description
Window
Diameter
Overall Dimensions
CT01
Current Sensor, NEMA
Starter Size 1, 3 phase,
27 amp
0.44" 4.625"x2.000"x1.375"
CT02
Current Sensor, NEMA
Starter Size 2&3, 3 phase,
90 amp
0.44" 4.625"x2.000"x1.375"
CT03
Current Sensor, NEMA
Starter Size 4, 3 phase,
200 amp
0.69"
5.60"x2.38"x1.72"
CT04
Current Sensor, NEMA
Starter Size 5, 1 phase,
300 amp
1.50"
4.50"x4.88"x4.68"
CT05
Current Sensor, NEMA
Starter Size 6, 1 phase,
600 amp
2.50"
4.57"x4.57"x4.68"
Order Code
Description
Window
Diameter
Overall Dimensions
GF01
Ground Fault Sensor 1&2,
20 amp, 3x 0.44" windows
0.44"
4.625"x2.000"x1.375"
GF02
Ground Fault Sensor 3&4,
20 amp, 1x 1.56" window
1.56"
3.53"x3.65"x2.23"
GF03
Ground Fault Sensor 5,
20 amp, 3x 2.08" windows
2.08"
9.00"x3.94"x2.23"
GF04
Ground Fault Sensor, Limit
Amp,
20 amp, 1x 2.5" window
2.5"
4.57"x4.57"x4.68"
GF05
Ground Fault Sensor, Limit
Amp,
20 amp, 1x 3.13" window
3.13"
4.63"x5.10"x5.50"
GF06
Ground Fault Sensor, Limit
Amp,
20 amp, 1x 4.62" window
4.62"
7.00"x7.12"x6.82"
Summary of Contents for LM10
Page 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Page 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Page 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...