CHAPTER 5: SETTINGS
PRODUCT SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-125
5
Figure 5-53: Control pushbutton logic
5.3.14 User-programmable pushbuttons
SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1(16)
USER PUSHBUTTON 1
PUSHBUTTON 1
FUNCTION: Disabled
Range: Self-Reset, Latched, Disabled
PUSHBTN 1 ID TEXT:
USER PB 1
Range: up to 20 alphanumeric characters
PUSHBTN 1 ON TEXT:
Range: up to 20 alphanumeric characters
PUSHBTN 1 OFF TEXT:
Range: up to 20 alphanumeric characters
PUSHBTN 1 HOLD:
0.0 s
Range: 0.0 to 10.0 s in steps of 0.1
PUSHBTN 1 SET:
Off
Range: FlexLogic operand
PUSHBTN 1 RESET:
Off
Range: FlexLogic operand
PUSHBTN 1 AUTORST:
Disabled
Range: Disabled, Enabled
PUSHBTN 1 AUTORST
DELAY: 1.0 s
Range: 0.2 to 600.0 s in steps of 0.1
PUSHBTN 1 REMOTE:
Off
Range: FlexLogic operand
PUSHBTN 1 LOCAL:
Off
Range: FlexLogic operand
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
Range: 0 to 60.00 s in steps of 0.05
PUSHBTN 1 LED CTL:
Off
Range: FlexLogic operand
PUSHBTN 1 MESSAGE:
Disabled
Range: Disabled, Normal, High Priority
PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled