MA-041
–
DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 68 of 99
Figure 9-51: R2 resistance measurement
Record the measurement as [
R2
It should be less than 2000 Ω and
within 5 % of the input channel impedance.
To verify the measurement, use the Factory Login, Press
BMT > Calibration
–
HF / LF
multipliers and Input Impedance
. An example of input impedance is shown in Figure
Figure 9-52: Calibration - Input Impedance
9.8.2.4.4
Total Resistance Test
Reconnect all the coaxial cables.
Retest the resistance across the two screws of the connector for each Bushing Adaptor
as shown in Figure 9-53.