SPS J2007003 L064 - Quick Start Guide
Document 850047442 r01 2015 July
2
Specifications and Application
Specifications and ordering information are in the
Slimline Power System Brochure
available at
www.gecriticalpower.com
Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an Integrated Ground Plane (Mesh-
Bonding Network or Common Bonding Network).
Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C).
Reference Documents
These documents are available at
www.gecriticalpower.com
.
Document Title
850035894
Galaxy Pulsar Edge Quick Start Guide
CC848815341
Pulsar Edge Controller Family Product Manual
Slimline Power System Brochure
4
Parameter Range
Default
Converter Internal Selective High
Output Voltage Shutdown
25.0 to 30.0V
29.0
High Output Voltage Major Alarm
25.0 to 30.0V
28.5
High Output Voltage Minor Alarm
24.0 to 30.0V
27.0
Output Voltage Set-Point
23.0 to 27.2V
26.0
Low Voltage Alarm
20.0 to 27.0V
23.0
Information: Controller Default Voltage Settings and Ranges
Input DC
Output DC
Voltage Current
3
Voltage Current
+24V Orange
EP0300DC24TEZ
48Vdc
9A max
24Vdc
11A
Converter
Information: Converter Options