Page 31
Intellix
™
BMT 330 User Manual
BMT330UM
v1.0
20-Jun-16
System Supervision
Figure 13: Alarm > System Supervision tab
Parameter
Suggested Value or Source of Data
High Comm CPU temperature
(sets the alarm trigger value)
Default= 75 deg C; (usual operating range -40 to
70 deg C)
High FPGA temperature
(sets the alarm trigger value)
Default= 75 deg C; (usual operating range -40 to
70 deg C)
Field devices comm error
Number of continuous failed comms attempts
before triggering alarm. Default=50
Inter CPU comm error
Number of continuous failed comms attempts
before attempting to recover the inter CPU
communication. If unsuccessful the alarm will be
triggered. Default=100
Neutral CT failure timeout
Period with PD activity on any phase (A, B or C)
but none on the neutral required to trigger
alarm. Default=48 hours