17
Integritas Wall Mount Charger
-
Quick Start Guide
Information: Battery Monitoring Connections
-
for use with NiCd and Lead acid batteries (VRLA, Flooded)
Battery Monitoring is accomplished with a
“
Daisy Chained
”
series of probes. The Probes monitor battery temperature. Bolt the Probe under
the
“
–
“
terminal connector hardware; NOT under the connecting lug.
Max per system: Probes
-
16.
Battery Temperature Measurement
Ordering Codes
Descriptions
Ordering
Codes
Descriptions
1600093513A
DTP873
-
Battery Thermal Probe
1600093512A
DTP873
-
Ambient Probe
Information Interlock Cable Recommendations
•
Wire
-
20
-
24 AWG
•
Mating Connector: Molex housing
-
43025
-
0200,
•
Terminals
-
Molex 43030
-
0008 (15µ
”
gold plated)
•
Hand Crimp Tool
-
Molex 0638190000
•
Insertion Tool
-
Molex 0638120800
•
Extraction Tool
-
Molex 0011030043