Parameterization errors
In order to determine what type of parameterization error has occurred, use the
corresponding software to access the controller online and read the error (see "Description
of the registers" on page A-17).
Proceed as follows,e.g., in the VersaSafe system:
•
The diagnostic LEDs indicate that an error has occurred.
•
Go online to the higher-level standard controller.
For each module of the VersaSafe island, a diagnostic register is mapped to the
process image of the IC220SDL953 (see "Description of the registers" on page A-17).
From this, determine the module of the safety island in which an error has occurred.
•
Evaluate the specified diagnostic code.
Table 8-7
Parameterization errors
Error cause
Diagnos-
tic code
(hex)
LED
Remark
Effect
Remedy
Acknow-
ledgment
Incorrect
parameteriza-
tion
See
FS
(flash-
ing)
Each output is pa-
rameterized individ-
ually
Module is in the safe
state
Check and correct
parameterization.
–
Table 8-8
Parameterization errors
Diagnostic code
Short description
Remedy
(hex)
(dec)
X23n
X230: OUT0_Ch1&2
X231: OUT1_Ch1&2
X232: OUT2_Ch1&2
X233: OUT3_Ch1&2
560
: OUT0_Ch1&2
561
: OUT1_Ch1&2
562
: OUT2_Ch1&2
563
: OUT3_Ch1&2
The parameterization of two related
outputs does not correspond to the
two-channel setting.
Correct value and resend parameter
data to the module.
X28n
X280: OUT0_Ch1
X281: OUT1_Ch1
X282: OUT2_Ch1
X283: OUT3_Ch1
X287: OUT0_Ch2
X288: OUT1_Ch2
X289: OUT2_Ch2
X28A: OUT3_Ch2
640
: OUT0_Ch1
641
: OUT1_Ch1
642
: OUT2_Ch1
643
: OUT3_Ch1;
647
: OUT0_Ch2
648
: OUT1_Ch2
649
: OUT2_Ch2
650
: OUT3_Ch2
The parameterized switch-off delay
time for the output is outside the per-
missible value range.
Correct value and resend parameter
data to the module.
X29n
X290: OUT0_Ch1&2
X291: OUT1_Ch1&2
X292: OUT2_Ch1&2
X293: OUT3_Ch1&2
656
: OUT0_Ch1&2
657
: OUT1_Ch1&2
658
: OUT2_Ch1&2
659
: OUT3_Ch1&2
For outputs parameterized for two-
channel operation, the same settings
were not assigned for the switch-off
delay.
Correct setting and resend parameter
data to the module.
X2Bn
X2B0: OUT0_Ch1&2
X2B1: OUT1_Ch1&2
X2B2: OUT2_Ch1&2
X2B3: OUT3_Ch1&2
688
: OUT0_Ch1&2
689
: OUT0_Ch1&2
690
: OUT0_Ch1&2
691
: OUT3_Ch1&2
For outputs parameterized for two-
channel operation, the same settings
were not assigned for enabling.
Correct setting and resend parameter
data to the module.
X2F2
754
At least one output with parameterized
switch-off delay is still performing a
switch-off operation.
Wait until the switch-off operation is
complete and resend parameter data
to the module.