Page 93
Hydran* M2-X Instruction Manual
MA-029
Rev. 1.0,
30-Jul-18
4.4.2
Setting the Parameters of the History Files
1.
Access
Setup > History Setup > History Log Rate
(see Section 3.2.6.1).
2.
Verify and set, as required, the
Short Term Rate
as well as the
Long Term #1
to
Long Term #4
logging hours.
3.
Press
Esc
, select
Clear HM2-X Hist File
and press
Enter
.
4.
Erase the content of the history files by selecting each option and pressing
Ok
.
4.4.3
Setting the Alarm Parameters
1.
Wait at least 30 minutes after powering up the Hydran M2-X or until the gas
and moisture levels read by the Hydran M2-X are stable
.
2.
Access
Alarms > Alarms Setup > Hydran Alarm Setup
(see Section 3.3.2.1).
Verify and set, as required, all parameters.
3.
Access
Alarms > Alarms Setup > H2O Alarm Setup
(see Section 3.3.2.2).
Verify and set, as required, all parameters.
4.
Access
Alarms > Alarms Setup > Temp Alarm Setup
(see Section 3.3.2.3).
Verify and set, as required, all parameters.
5.
Access
Alarms > Alarms Setup > Battery Alarm Setup
(see Section 3.3.2.4).
Verify and set, as required, all parameters.
6.
Access
Alarms > Alarms Setup > Analog Input Alarm Setup
(see Section
3.3.2.5). Verify and set, as required, all parameters.
7.
Access
Alarms > Alarms Setup > Sys. Fault Trigger
(see Section 3.3.2.6).
Verify and set, as required, all parameters.
4.4.4
Verifying the Battery Voltage
1.
Access Service > View Service Data.
2.
Verify the battery voltage (
Battery
) exceeds 2.85 V; if it is below 2.85 V, replace
the battery (see Appendix G). For the battery specifications, see Section 9.3.1.
4.4.5
Setting the Dynamic Oil Sampling System Parameters
1.
Access
Setup > Temp. Setup
(see Section 3.2.4).
2.
Verify and set, as required, the dynamic oil sampling system parameters. For
more information, see Section 3.2.4.
3.
Clear the Sensor Hist File.