Page 51
Hydran* M2-X Instruction Manual
MA-029
Rev. 1.0,
30-Jul-18
(parameter
Alarm
Delay
); when an alarm condition is detected, the relay assigned to
this alarm condition
(parameters
Alarm Hi Relay
and
Alarm Hi-Hi Relay
) is activated.
The parameters in
Alarms Setup
are also located in
Setup > Alarms Setup
.
3.3.2.1
Hydran Alarms Setup
•
The
Hydran Alarm Setup
functions give access to the parameters of the gas
alarm conditions:
–
Alarm Hi SP
: Set point of the gas level High alarm condition.
–
Alarm Hi-Hi SP
: Set point of the gas level High-High alarm condition.
–
Alarm Delay
: Alarm delay for both set points.
–
Alarm Hi Relay
: Relay activated when a gas level High alarm condition is
detected.
–
Alarm Hi-Hi Relay
: Relay activated when a gas level High-High alarm
condition is detected.
•
Hydran Hourly Trend Alarm
: Gives access to the hourly trend High and High-
High
alarm parameters:
–
Alarm Hi SP
: Set point of the hourly trend High alarm condition.
–
Alarm Hi-Hi SP
: Set point of the hourly trend High-High alarm condition.
–
Alarm Delay
: Alarm delay for both set points. This delay is calculated in
percentage of the hourly trend period; see parameter
Hourly Tr. Period
in
Setup > Reading Setup > Gas Reading Setup
–
Alarm Hi Relay
: Relay activated when a gas hourly trend High alarm
condition is detected.
–
Alarm Hi-Hi Relay
: Relay activated when a gas hourly trend High-High alarm
condition is detected.
•
Hydran Daily Trend Alarm
: Gives access to the daily trend High and High-High
alarm
parameters:
–
Alarm Hi SP
: Set point of the daily trend High alarm condition.
–
Alarm Hi-Hi SP
: Set point of the daily trend High-High alarm condition.
–
Alarm Delay
: Alarm delay for both set points. This delay is calculated in
percentage of the daily trend period; see parameter
Daily Tr. Period
in
Setup
> Reading Setup
> Gas Reading Setup
–
Alarm Hi Relay
: Relay activated when a gas daily trend High alarm condition
is detected.
–
Alarm Hi-Hi Relay
: Relay activated when a gas daily trend High-High alarm
condition is detected.
•
Hydran Sensor Temp Alarm
: See
Alarms Setup > Temp. Alarm Setup > Sensor
Temp. Alarm
Note: Each alarm of the Hydran M2-X can be assigned to any one of the four relays (1
to 4). More than one alarm can be assigned to a same relay. Appendix I presents the
list of all alarm messages that can appear in the Perception software.
3.3.2.2
Moisture Alarms Setup