Chapter 12 • Troubleshooting
12-12
Rev. 6, March 2011
Part 17997
12.1.20 SensTemp H
•
Alarm type
: Fail alarm
•
Non-abbreviated description
: Sensor temperature High
•
Priority
: Low
•
Parameter(s) involved
:
–
SensTemp H
;
SysOK Relay;FaultTrig.
submenu; Section 4.5.7 on page 4-23
–
STempAlr H
(alarm set point);
Temperature
submenu; Section 4.5.3 on page 4-17
–
TempoAlr Delay
;
Temperature
submenu; Section 4.5.3 on page 4-17
•
Alarm cause(s)
: Temperature of the Hydran 201 sensor above the
STempAlr H
alarm
set point
Although the H201 sensor is not affected by the temperature, monitor its temperature
regularly.
12.1.21 SensTemp HH
•
Alarm type
: Fail alarm
•
Non-abbreviated description
: Sensor temperature High-High
•
Priority
: Medium
•
Parameter(s) involved
:
–
SensTemp HH
;
SysOK Relay;FaultTrig.
submenu; Section 4.5.7 on page 4-23
–
STempAlr HH
(alarm set point);
Temperature
submenu; Section 4.5.3 on page 4-17
–
TempoAlr Delay
;
Temperature
submenu; Section 4.5.3 on page 4-17
•
Alarm cause(s)
: Temperature of the Hydran 201 sensor above the
STempAlr HH
alarm
set point
Proceed as follows:
1.
The oil is probably too hot at the location where the H201 sensor is installed; install
the Hydran 201T
i
at another location on the transformer tank, preferably at the
bottom. For details on typical installations, see Section 5.2.2.2 on page 5-10.
2.
If not already done, install the finned, high-temperature adaptor shown in Figure B-6
on page B-4; it can be purchased from General Electric Canada.
CAUTION
WARNING
Exposing the H201 sensor to temperatures above the STempAlr HH
alarm set point can damage the sensor.
Summary of Contents for Hydran 201i
Page 1: ...GE Energy Services Digital Energy Hydran Instruction Manual 201i System ...
Page 6: ...Instruction Manual vi Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 8: ...Instruction Manual viii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 22: ...Instruction Manual xxii Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 36: ...Chapter 1 Introduction 1 10 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 114: ...Chapter 5 Before Installation 5 16 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 143: ...Installation Part 17997 Rev 6 March 2011 6 29 Figure 6 9 Installing the CPU Module ...
Page 236: ...Chapter 12 Troubleshooting 12 20 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 244: ...Chapter 13 Maintenance 13 8 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 254: ...Appendix B Mechanical Drawings B 2 Rev 6 March 2011 Part 17997 Figure B 3 1 5 In Adaptor ...
Page 255: ...Hydran 201Ti Intelligent Transmitter Part 17997 Rev 6 March 2011 B 3 Figure B 4 1 In Adaptor ...
Page 284: ...Appendix G Unit Conversions G 2 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 298: ...Appendix I Glossary I 12 Rev 6 March 2011 Part 17997 PAGE LEFT INTENTIONALLY BLANK ...
Page 299: ......