GTD45GASJ 

GE

® 

Series 7.2 cu. ft. capacity Aluminized alloy drum gas 

dryer with HE Sensor Dry

Specification Created 7/15

For answers to your Monogram,

® 

GE Profile

 or GE

®

 appliance questions, visit our 

website at geappliances.com or call GE Answer Center

®

 service, 800.626.2000.

FOR COMPLETE INFORMATION, SEE INSTALLATION INSTRUCTIONS 

PACKED WITH YOUR DRYER.
DUCTING MATERIALS:

 

For best performance, this dryer should be vented with 4" diameter all 
rigid metal exhaust duct. If rigid metal duct cannot be used, then UL-listed 
flexible metal (semi-rigid) ducting can be used (Kit WX08X10077). In special 
installations, it may be necessary to connect the dryer to the house vent using 
a flexible metal (foil-type) duct. A UL-listed flexible metal (foil-type) duct 
may be used ONLY in installations where rigid metal or flexible metal (semi-
rigid) ducting cannot be used AND where a 4” diameter can be maintained 
throughout the entire length of the transition duct. Please see installation 
instruction packed with your dryer for complete instructions when using flexible 
metal (foil type) ducting. 

EXHAUST LENGTH CALCULATION:

 

1.   Determine the number of 90° turns needed for your installation. If you 

exhaust to the side or bottom of dryer, add one turn.

2.   The maximum length of 4" rigid (aluminum or galvanized) duct which can 

be tolerated is shown in the table. A turn of 45° or less may be ignored. Two 
45° turns within the duct length should be treated as a 90° elbow. A turn 
over 45° should be treated as a 90° elbow.

Dryers must be exhausted to the outside.

CAUTION:

 For personal safety do not terminate exhaust into a chimney, under 

any enclosed house floor (crawl space), or into an attic, since the accumulated 
lint could create a fire hazard or moisture could cause damage. Never terminate 
the exhaust into a common duct or plenum with a kitchen exhaust, since the 
combination of lint and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back 
drafts, bird nesting, etc. The wall cap must also be located at least 12" above 
the ground or any other obstruction with the opening pointed down.

FOR MORE INFORMATION ON VENTING KITS AND ACCESSORIES, 

PLEASE CALL 1-800-GE-CARES

.

DRYER EXHAUSTING INFORMATION—USE METAL DUCT 

ONLY VERTICAL AND HORIZONTAL DUCTING

A

B

2-1/2

4

GE Dryer Vent

A

B

2-1/2

4

GE Dryer Vent

A

BEST PERFORMANCE

Maximum length  
of 4" dia rigid  
metal duct
Exhaust hood type

Domestic dryer models 

Number of 

90° turns

A

4" opening

B

2-1/2" opening

GE Frontload Long Vent 7.0 
cu. ft. capacity electric dryer 
(GFDL)

0

200 ft.

175 ft.

1

185 ft.

165 ft.

2

175 ft.

155 ft.

3

165 ft.

145 ft.

4

155 ft.

135 ft.

5

145 ft.

125 ft.

Long Vent 6.0 - 8.0 cu. ft.  
capacity electric & gas dryers 
(GTDL and GTV)

0

150 ft.

125 ft.

1

135 ft.

115 ft.

2

125 ft.

105 ft.

3

115 ft.

95 ft.

4

105 ft.

85 ft.

5

95 ft.

75 ft.

Long Vent 7.0 cu. ft. capacity 
electric & gas (GTD42, GTD45, 
GTD65, GTX42 and GTX60)

0

120 ft.

90 ft.

1

100 ft.

75 ft.

2

85 ft.

65 ft.

3

70 ft.

55 ft.

4

60 ft.

45 ft.

5

55 ft.

35 ft.

All 6.0 - 8.3 cu. ft. capacity 
models electric and gas dryers 
(GFDS, GFDR, GFDN, GTDS, 
GTDN, GHDN, GHDS, GTDP, 
GLDP, GTD, HTDP, HTDX)

0

90 ft.

60 ft.

1

60 ft.

45 ft.

2

45 ft.

35 ft.

3

35 ft.

25 ft.

4

25 ft.

15 ft.

DCVH480

0

90 ft.

60 ft.

1

60 ft.

45 ft.

2

45 ft.

35 ft.

3

35 ft.

25 ft.

All 3.6 cu. ft. (DSKS, DSKP)
electric dryers

0

46 ft.

37 ft.

1

37 ft.

30 ft.

2

30 ft.

22 ft.

3

23 ft.

15 ft.

Laundry Center GUD27

0

56 ft.

42 ft.

1

48 ft.

34 ft.

2

40 ft.

26 ft.

3

32 ft.

18 ft.

Laundry Center GUD24

0

43 ft.

36 ft.

1

33 ft.

26 ft.

2

24 ft.

16 ft.

Summary of Contents for GTD45GASJ

Page 1: ...ee installation instructions packed with your dryer DIMENSIONS AND INSTALLATION INFORMATION IN INCHES SPECIAL INSTALLATION REQUIREMENTS ALCOVE OR CLOSET INSTALLATION If your dryer is approved for installation in an alcove or closet it will be stated on a label on the dryer back The dryer MUST be exhausted to the outside Minimum clearances between dryer cabinet and adjacent walls or other surfaces ...

Page 2: ...estions visit our website at geappliances com or call GE Answer Center service 800 626 2000 22 1 2 29 1 2 27 3 1 2 1 3 4 3 1 4 8 37 1 2 42 1 2 27 5 Power Cord 4 1 2 11 3 4 Side View Rear View 5 7 cu ft Dryers 2 Back View Power Cord Hole 30 1 2 5 8 6 0 and 7 0 cu ft Dryers 5 Back View Power Cord Hole 4 1 2 POWER CORD LOCATIONS DIMENSIONS AND INSTALLATION INFORMATION IN INCHES ...

Page 3: ...e floor crawl space or into an attic since the accumulated lint could create a fire hazard or moisture could cause damage Never terminate the exhaust into a common duct or plenum with a kitchen exhaust since the combination of lint and grease could create a fire hazard Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts bird nesting etc The wall cap must also be locate...

Page 4: ...temperature with a sensor bar that measures moisture to prevent over drying Up to 120 ft venting capability Provides flexible installation Extended Tumble Freshly tumbles your garments periodically for up to 8 hours when unable to move clothing to the dryer right away End of cycle signal Alerts you when the load is done so clothes can be removed before wrinkles set in Model GTD45GASJWS White with ...