Chapter 7 Earthing and Shielding
GFK-2958E
RSTi-EP User Manual
334
7.3
Electromagnetic Compatibility (EMC)
RDTi-EP products completely meet EMC requirements. EMC planning, however, is necessary prior to
installation.
Aspects to consider include all potential interference sources such as galvanic, inductive and
capacitive couplings, as well as radiation couplings.
7.3.1
Ensuring EMC
To ensure EMC, the following basic principles must be observed during installation of the RSTi-EP
modules:
•
Proper, extensive earthing of inactive metal parts
•
Correct shielding of cables and equipment
•
Proper layout of wires
–
cabling
•
Creation of a uniform reference potential and earthing of all electrical equipment
•
Special EMC measures for special applications (e.g. frequency converters, servo drives)
•
Contactors and relay coils must be equipped with the corresponding interference
suppressors
7.3.2
Earthing of Inactive Metal Parts
The earthing of all inactive metal parts reduces the influence of coupled interference. For this
purpose, all inactive metal parts (such as switch cabinets, cabinet doors, support beams, mounting
plates, DIN rails, etc.) must be connected to each other over a large surface area with low
impedance, whereby a uniform reference potential is ensured for all control unit elements.
Required measures:
•
Removal of the insulating layer around screw connections. Protection of connection points
against corrosion
•
Connection of moving earthed components (cabinet doors, separated mounting plates, etc.)
through short earthing straps with large surfaces
•
When possible, avoid using aluminium parts, because aluminium oxidises easily and in this
respect is unsuited for earthing
7.3.3
PE connection
The connection from earth to the PE (protective earth) connection must be done centrally.
Warning
In the event of a fault, the earth must never take on a dangerous contact
voltage, which is why it must be connected to a PE conductor.
Summary of Contents for GFK-2958E
Page 1: ...RSTi EP User Manual GFK 2958E November 2017 ...
Page 23: ...Chapter 1 Introduction GFK 2958E RSTi EP User Manual 19 Notes ...
Page 56: ...Chapter 3 Configuration GFK 2958E RSTi EP User Manual 52 Notes ...
Page 183: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 179 EP 5111 ...
Page 184: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 180 EP 5111 ...
Page 316: ...Chapter 5 Detailed Descriptions of I O Modules GFK 2958E RSTi EP User Manual 312 Notes ...
Page 330: ...Chapter 6 Installation GFK 2958E RSTi EP User Manual 326 Notes ...
Page 344: ...Chapter 7 Earthing and Shielding GFK 2958E RSTi EP User Manual 340 ...
Page 345: ...Chapter 7 Earthing and Shielding GFK 2958E RSTi EP User Manual 341 Notes ...
Page 385: ...Chapter 8 Web Server GFK 2958E RSTi EP User Manual 381 Notes ...
Page 401: ...Chapter 11 Disassembly and Disposal GFK 2958E RSTi EP User Manual 397 Notes ...
Page 413: ...Chapter 12 LED Indicators and Troubleshooting GFK 2958E RSTi EP User Manual 409 Notes ...
Page 416: ...Chapter 14Accessories and Replacement Parts GFK 2958E RSTi EP User Manual 412 Notes ...