background image

CONNECTING A GAS DRYER (cont.)

Installation Instructions

DRYER GAS SUPPLY CONNECTION

GAS SUPPLY

 

A 1/8” National Pipe Taper thread plugged 

tapping, accessible for test gauge connection, 

must be installed immediately upstream of the 

gas supply connection to the dryer. Contact 

your local gas utility should you have questions 

on the installation of the plugged tapping.

 

Supply line is to be 1/2” rigid pipe and equipped 

with an accessible shutoff within 6 feet of, and 

in the same room with, the dryer.

 

Use pipe thread compound appropriate for 

natural or LP gas or use PTFE tape.

 

Connect flexible metal connector to dryer and 

gas supply.

ADJUSTING FOR ELEVATION

 

Gas clothes dryers input ratings are based on 

sea level operation and need not be adjusted 

for operation at or below 2000 ft. elevation. For 

operation at elevations above 2000 ft., input 

ratings should be reduced at a rate of 4 percent 

for each 1000 ft. above sea level. 

 

Installation must conform to local codes and 

ordinances or, in their absence, the NATIONAL 

FUEL GAS CODE, ANSI Z223.

•   You must use with this dryer a flexible metal 

connector (listed connector ANSI Z21.24/CSA 6.10). 

The length of the connect shall not exceed 3 ft.

6

2"

2-5/8"

3/8"

 NPT MALE THREAD GAS SUPPLY

NOTE: Add to vertical dimension
the distance between cabinet
bottom to floor.

GAS REQUIREMENTS

- Explosion Hazard

WARNING

•   Use a new CSA International approved flexible 

gas supply line. Never reuse old flexible 

connectors.

•   Install an individual manual shut-off valve 

within 6ft. of the dryer in accordance with the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54.

•   Securely tighten all gas connections.
•   If connected to LP gas, have a qualified person 

make sure gas pressure 

DOES NOT

 exceed 13” 

water column.

•   Examples of a qualified person include: licensed 

heating personnel, authorized gas company 

personnel, and authorized service personnel.

•   Failure to do so can result in death, explosion, 

or fire.

 

The installation must conform with local codes, 

or in the absence of local codes, with the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, 

or the Natural Gas and Propane Installation 

Code, CSA B149.1.

- Fire Hazard

WARNING

FOR USE WITH NATURAL GAS ONLY

Dryer as produced by manufacturer is to be used only 

with a natural gas supply. A manufacturer-supplied 

conversion kit is required to convert this dryer for 

propane gas supply. Use propane gas conversion 

kit WE25X217. Conversion must be made by properly 

trained and qualified personnel in accordance with 

local codes and ordinances.

Summary of Contents for GFD45ESPK0DG

Page 1: ... Appliances at 800 GE CARES 800 432 2737 or visit our Web site at GEAppliances com Fire Hazard WARNING Clothes dryer installation must be performed by a qualified installer Install the clothes dryer according to these instructions and local codes DO NOT install a clothes dryer with flexible plastic venting materials If flexible metal semi rigid or foil type duct is installed it must be UL listed a...

Page 2: ...er supply hoses Hoses degrade over time and need to be replaced every 5 years to reduce the risk of hose failures and water damage Parts and Accessories Order on line at GEApplianceParts com 24 hours a day or by phone at 800 626 2002 during normal business hours STEAM WATER HOSES for steam dryer models only Part Number Type Length Amperage WX9X2 3 Prong 4 Feet 30 WX9X3 3 Prong 5 Feet 30 WX9X4 3 Pr...

Page 3: ... the floor for a garage installation Failure to do so can result in death explosion or fire The dryer MUST be vented to the outdoors See the EXHAUSTING THE DRYER section Minimum clearance between dryer cabinet and adjacent walls or other surfaces is 0 either side 1 front 1 rear 1 top Consideration must be given to provide adequate clearance for installation and service Closet doors must be louvere...

Page 4: ...on at the same time NOTE Use new inlet hoses never use old hoses 1 Turn the cold water faucet off Remove the washer inlet hose from the washer fill valve connector cold 2 Ensure the rubber flat washer is in place and attach one female coupling of the short hose provided onto the washer fill valve connector Tighten by hand until firmly seated 3 Attach one male end of the Y connector to the other fe...

Page 5: ... and discard old flexible gas connector and ducting material Shut off Valve 5 TOOLS YOU WILL NEED MATERIALS YOU WILL NEED 10 Adjustable wrenches 2 8 Pipe wrench Flat blade screwdriver Level Slip joint pliers 4 dia metal elbow Pipe compound or PTFE tape Flexible gas line connector Duct clamps 2 or Spring clamps 2 Safety glasses 4 dia metal duct recommended 4 Cover Plate Kit WE49X22606 4 dia UL list...

Page 6: ...gth of the connect shall not exceed 3 ft 6 2 2 5 8 3 8 NPT MALE THREAD GAS SUPPLY NOTE Add to vertical dimension the distance between cabinet bottom to floor GAS REQUIREMENTS Explosion Hazard WARNING Use a new CSA International approved flexible gas supply line Never reuse old flexible connectors Install an individual manual shut off valve within 6ft of the dryer in accordance with the National Fue...

Page 7: ...ff valve F Apply pipe compound or PTFE tape to all male threads Shut Off Valve Plugged Tapping CONNECTING THE DRYER TO THE GAS SUPPLY Install a female 3 8 NPT elbow at the end of the dryer gas inlet Install a 3 8 flare union adapter to the female elbow IMPORTANT Use a pipe wrench to securely hold on to the end of the dryer gas inlet to prevent twisting the inlet NOTE Apply pipe compound or PTFE ta...

Page 8: ...fore use GROUNDING INSTRUCTIONS This dryer must be grounded In the event of a malfunction or breakdown grounding will reduce the risk of electric shock by providing a path of least resistance for electric current This dryer uses a cord having an equipment grounding conductor and a grounding plug The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordan...

Page 9: ...OFF THE TERMINAL BLOCK 9 MATERIALS YOU WILL NEED 4 dia metal elbow 3 4 Strain relief UL recognized 4 Duct clamps 2 or 4 spring clamps 2 Safety glasses 4 dia metal duct recommended 4 Cover plate Kit WE49X22606 Gloves Exhaust hood Duct tape TOOLS YOU WILL NEED Slip joint pliers Flat blade screwdriver Phillips screwdriver Level 4 dia UL listed flexible metal duct if needed Dryer power cord kit not pr...

Page 10: ... fire or electrical shock GROUNDING INSTRUCTIONS For a grounded cord connected dryer This dryer must be grounded In the event of a malfunction or breakdown grounding will reduce the risk of electric shock by providing a path of least resistance for electric current This dryer uses a cord having an equipment grounding conductor and a grounding plug The plug must be plugged into an appropriate outle...

Page 11: ...ired by local code install external ground not provided to grounded metal cold water pipe or other established ground determined by a qualified electrician L1 N L2 RELOCATE GREEN GROUND SCREW HERE STRAIN RELIEF BRACKET GREEN OR YELLOW WIRE 3 4 UL RECOGNIZED STRAIN RELIEF HOT WIRE SCREWS 3 HOT WIRE COVER NEUTRAL White REMOVE GROUND STRAP AND DISCARD KEEP GREEN GROUND SCREW 4 10 AWG MINIMUM COPPER C...

Page 12: ...that comply with UL 2158A STANDARD FOR CLOTHES DRYER TRANSITION DUCT shall be used Avoid resting the duct on sharp objects For best drying performance 1 Slide one end of the duct over the clothes dryer outlet pipe 2 Secure the duct with a clamp 3 With the dryer in its permanent position extend the duct to its full length Allow 2 of duct to overlap the exhaust pipe Cut off and remove excess duct Ke...

Page 13: ...45 elbows will be treated like one 90 elbow For every additional 90 elbow reduce the allowable vent system length by 10 feet When calculating the total vent system length you must add all the straight portions and elbows of the system including the transition duct EXHAUST LENGTH 13 DO NOT bend or collapse ducting Use elbows if turns are necessary DO NOT use excessive exhaust length Cut duct as sho...

Page 14: ...life Termination should present minimal resistance to the exhaust airflow and should require little or no maintenance to prevent clogging Wall caps must be installed at least 12 above ground level or any other obstruction with the opening pointed down SEPARATION OF TURNS For best performance separate all turns by at least 4 ft of straight duct including distance between last turn and dampened wall...

Page 15: ...HT SIDE OF CABINET Preassemble 4 elbow with 4 duct Wrap duct tape around joint Insert duct assembly elbow first through the side opening and connect the elbow to the dryer internal duct Be sure not to pull or damage the electrical wires inside the dryer when inserting the duct Fixing hole A 13 1ø2 34 29cm TAB LOCATION Fire Hazard WARNING Close the back opening with cover plate Kit WE49X22606 Disco...

Page 16: ...lbow and the bottom duct Internal duct joints must be secured with tape otherwise they may separate and cause a safety hazard Duct tape FINAL SETUP LEVEL THE DRYER Stand the dryer upright near the final location and adjust the four leveling legs at the corners to ensure that the dryer is level from side to side and front to rear Lower Raise PLUG DRYER IN 1 2 DRYER START UP Press the Power button N...

Page 17: ...ación 04 Si tiene alguna pregunta llame GE Appliances a 800 GE CARES 800 432 2737 o visite nuestro sitio Web en GEAppliances com ADVERTENCIA Riesgo de incendio La instalación de la secadora debe efectuarla un instalador calificado Instale la secadora de ropa de acuerdo con estas instrucciones y en cumplimiento con los códigos locales NO instale una secadora de ropa con conductos de plástico flexib...

Page 18: ...ministro de agua Con el paso del tiempo las mangueras se degradan y deben ser reemplazadas cada 5 años a fin de reducir el riesgo de fallas sobre las mismas y daños con el agua Piezas y Accesorios Ordene hoy a través de Internet en GEAppliancesparts com las 24 horas del día o en forma telefónica llamando al 800 626 2002 durante el horario comercial habitual MANGUERA DE VAPOR Y AGUA sólo para los m...

Page 19: ...ncendio o la muerte Esta secadora DEBE tener una ventilación al exterior Ver la sección SALIDA AL EXTERIOR DE LA SECADORA El espacio libre mínimo entre la secadora y las paredes adyacentes u otras superficies es 0 en ambos lados 1 en el frente 1 en la parte trasera 1 en la parte superior Se deberá considerar que se debe brindar el despeje adecuado para la instalación y el servicio técnico Las puer...

Page 20: ...asta que esté firmemente asentada 5 Asegúrese de que la arandela de goma plana se encuentra en su posición y coloque una manguera de entrada de agua de 4 a 6 pies de largo puede ser necesario comprarla por separado a un extremo macho del conector Y Apriete con la mano hasta que quede firmemente asentado 6 Asegúrese de que la arandela plana de goma se encuentre en su lugar y sujete el otro extremo ...

Page 21: ...exible de gas y el material del conducto Válvula de cierre HERRAMIENTAS NECESARIAS MATERIALES NECESARIOS Llaves ajustables de 10 2 Llave para tubos de 8 Destornillador de lados planos Nivel Pinzas Codo de metal de 4 diámetro Compuesto o PTFE cinta para tuberías Conector de tubería de gas flexible Abrazaderas de tubería 2 o abrazaderas de resorte 2 Gafas de seguridad Conducto de metal de 4 diámetro...

Page 22: ...O DE GAS ROSCA MACHO NPT DE 3 8 NOTA Agregue a la dimensión vertical la distancia entre la parte inferior del gabinete y el piso REQUERIMIENTOS DE GAS Riesgo de explosión ADVERTENCIA Use una línea nueva de suministro de gas flexible que esté aprobada por CSA International Nunca vuelva a usar conectores flexibles viejos Instale una válvula de cierre manual individual dentro de 6 pies de la secadora...

Page 23: ...E en todas las roscas macho Válvula de apagado Toma a rosca CÓMO CONECTAR LA SECADORA AL SUMINISTRO DE GAS Instale un codo hembra NPT de 3 8 al final de la entrada de gas de la secadora Instale un adaptador de unión cónica de 3 8 al codo hembra IMPORTANTE Utilice una llave para tubos para sostener bien el extremo de la entrada de gas de la secadora para no doblar la entrada NOTA Aplique compuesto ...

Page 24: ...correctamente polarizado y conectado a tierra interruptor de 15 o 20 amperios o un fusible de retardo Potencia 2 hilos más la tierra 120 voltios monofásica 60 Hz corriente alterna Tomacorriente de salida Receptáculo de 3 clavijas debidamente conectado a tierra deberán colocarse de modo que el cable de alimentación esté accesible cuando la secadora está instalada en su posición final Si el circuito...

Page 25: ...RIALES NECESARIOS Codo de metal de 4 de diámetro Alivio de tensión de 3 4 reconocido por UL Abrazaderas de tubería de 4 2 o abrazaderas de resorte de 4 2 Gafas de seguridad Conducto de metal de 4 de diámetro recomendado 4 Placa de cubierta Kit WE49X22606 Guantes Campana de salida Cinta aislante HERRAMIENTAS NECESARIAS Pinzas Destornillador de lados planos Destornillador Phillips Nivel Conducto de ...

Page 26: ...NSTRUCCIONES DE CONEXIÓN A TIERRA Para una secadora conectada con cable con conexión a tierra Esta secadora deberá estar conectado a tierra En caso de mal funcionamiento o avería la conexión a tierra reducirá el riesgo de descargas eléctricas al brindar un camino con una resistencia menor para la corriente eléctrica Esta secadora está equipada con un cable con un conductor para la conexión a tierr...

Page 27: ... tomacorriente 3 Quite la tapa del cable de energía ubicada en la parte trasera inferior 4 Quite y descarte la cinta de conexión a tierra Conserve el tornillo verde de conexión a tierra para el paso 7 5 Instale un alivio de tensión de 3 4 pulgadas reconocido por UL en el orificio de entrada del cable de energía Pase el cable de energía a través del alivio de tensión 6 Conecte el cable de energía d...

Page 28: ... Evite que la tubería se apoye sobre objetos cortantes Para un mejor funcionamiento 1 Deslice un extreme del conducto sobre la tubería de salida de la secadora de ropa 2 Asegure el conducto con una abrazadera 3 Con la secadora en su posición permanente extienda el conducto hasta su máxima extensión Permita que 2 del conducto se superpongan con la tubería de escape Corte y retire el sobrante del co...

Page 29: ...o de 90º Dos codos de 45 deberán ser considerados como un codo de 90 Paracadacodoadicionalde90 reduzcaen10piesla longitud permisible del sistema de escape En el cálculo de la longitud total del sistema de ventilación debe agregar todas las partes rectas y codos del sistema incluyendo el conducto de transición LONGITUD DE SALIDA NO doble o pliegue los conductos Utilice codos si algunos codos result...

Page 30: ... debe presentar una resistencia mínima al flujo de salida y debe requerir poco mantenimiento para evitar las obstrucciones Las cubiertas de pared deben instalarse por lo menos a 12 sobre el nivel del suelo o cualquier otra obstrucción con la abertura apuntando hacia abajo SEPARACIÓN DE CURVAS Para un mejor desempeño separe todas las curvas con 4 pies de conducto recto como mínimo incluyendo la dis...

Page 31: ...otectores para brazos Si esto no se cumple se podrá producir una incendio descarga eléctrica o laceraciones ADVERTENCIA Riesgo de incendio Quite el tornillo y consérvelo Quite la tapa deseada sólo una Derecha sólo modelos a eléctrico Izquierda Parte inferior Gire la lengüeta hasta 45 No para gas Vuelva a conectar la porción cortada A del conducto a la caja del ventilador Asegúrese de que el conduc...

Page 32: ... TAPE Cinta aislante Introduzca el codo a través de la abertura trasera y conéctelo al conducto interno de la secadora Aplique cinta aislante como puede verse en la junta entre el conducto interno de la secadora y el codo y también en la junta entre el codo y el conducto inferior Las juntas del conducto interno deben sujetarse con cinta caso contrario pueden separarse y provocar un riesgo de segur...

Reviews: